Maytag WINSLOW PI40 User Manual

Page 8

Advertising
background image

8

Control Board Installation

The Winslow PI40 insert is shipped with the control board wrapped and
placed behind the firebox. To install the control board, unwrap it and
the right side surround panel found in the surround kit. There are four
prongs protruding from the surround. Place the two slots in the bottom
and the two holes in the top of the control board over the four prongs
on the surround panel. Install the surround panels following the instruc-
tions on Page 10.

Venting

Pellet pipe type PL, L, or listed pellet flex liner must be used to vent the
Winslow™ PI40 insert. The insert’s flue collar is 3” in diameter. The insert’s
combustion blower pressurizes and pushes flue gases out the pellet pipe.
All pipe joints should be locked together or screwed with three screws if
the pipe does not have a locking system. The pipe joints can be sealed
with high temperature silicone if there is a possibility of flue gases leaking
into the living area. The pipe should be fastened with three screws to the
insert’s flue collar. The longer the run of pipe and the more elbows used,
the greater the resistance to the flow of flue gases. Four inch diameter
pellet pipe is recommended for pipe runs greater than 15 feet or when a
number of elbows are used. A 3-4” increaser can be used to connect the
4” pipe to the 3” flue collar. The outside air pipe may run up the chimney,
horizontally, or down provided the structural integrity of the fireplace and
chimney system are maintained. DO NOT INSTALL A FLUE DAMPER IN
THE EXHAUST VENTING SYSTEM OF THIS UNIT. DO NOT CONNECT THIS
UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

Vent Termination Requirements:

If the insert is not vented vertically, the following apply:

1. Do not terminate the vent in any enclosed or semi-enclosed areas

such as a carport, garage, attic, crawlspace, narrow walkway, closely

fenced area, under a sundeck or porch, or any location that can build

up a concentration of fumes such as stairwells, covered breezeway,

etc.

2. Vent surfaces can become hot enough to cause burns if touched.

Non-combustible shielding or guards may be required.

3. Termination must exhaust above the inlet elevation. It is recommended

that at least five feet of vertical pipe be installed outside when the

insert is vented directly through a wall. This will create a natural draft

to prevent the possibility of smoke or odor during appliance shut

down or power failure and avoid exposing people or shrubs to high

temperatures.

4. The vent should terminate no less than four feet below, no less than

four feet horizontally from, and no less than one foot above doors

and windows, or gravity/ventilation air inlets into the building.

5. The distance between the bottom of termination and grade should be

12” minimum. The distance between the bottom of the termination

and a public walkway should be a minimum of seven feet.

6. Locate the vent termination at least two feet away from combustible

materials such as shrubs, plants, grass, fences, roof overhangs, and

adjacent buildings.

INSTALLATION

Advertising