Electrical service guide for 240 vac, Extension cord data, Caution – Miller Electric 375 X-TREME User Manual

Page 16: 8. electrical service guide for 240 vac, 9. extension cord data

Advertising
background image

.

A complete Parts List is available at www.MillerWelds.com

OM-225 216 Page 12

4-8.

Electrical Service Guide For 240 VAC

Y

CAUTION:

INCORRECT INPUT POWER can damage this welding power source. This welding power

source requires a CONTINUOUS supply of 60 Hz (

+

10%) power at

+

10% of rated input voltage. Phase

to ground voltage shall not exceed +10% of rated input voltage. Do not use a generator with automatic
idle device (that idles engine when no load is sensed) to supply input power to this welding power
source.

Actual input voltage should not exceed

±

10% of indicated required input voltage. If

actual input voltage is outside of this range, output may not be available.

NOTE

60 Hz

Single
Phase

Input Voltage

240

Input Amperes At Rated Output

13.9

Max Recommended Standard Fuse Rating In Amperes

Circuit Breaker

1

, Time-Delay

2

15

Normal Operating

3

20

Min Input Conductor Size In AWG

4

14

Max Recommended Input Conductor Length In Feet (Meters)

91

(28)

Min Grounding Conductor Size In AWG

4

14

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

Y

Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.

4-9.

Extension Cord Data

When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.

NOTE

Input Voltage

Input Power

Phase

Hertz

Conductor Size

Max. Cord Length

120 V

1

60

14 AWG

22 ft (7 m)

240 V

1

60

14 AWG

91 ft (28 m)