10. connecting 1-phase input power for 240 vac – Miller Electric 375 X-TREME User Manual

Page 17

Advertising
background image

.

A complete Parts List is available at www.MillerWelds.com

OM-225 216 Page 13

4-10. Connecting 1-Phase Input Power For 240 VAC

803 766-B / Ref. 802 443-A

Y

Installation must meet all
National and Local Codes − have
only qualified persons make this
installation.

Y

Disconnect and lockout/tagout
input power before connecting
input conductors from unit.

Y

Always connect green or green/
yellow conductor to supply
grounding terminal first, and never
to a line terminal.

1

Black And White Input Conductor
(L1 And L2)

2

Green Or Green/Yellow Grounding
Conductor

3

Input Power Cord.

4

Disconnect Device (switch shown in
the OFF position)

5

Disconnect Device Grounding
Terminal

6

Disconnect Device Line Terminals

Connect green or green/yellow grounding
conductor to disconnect device grounding
terminal first.

Connect input conductors L1 and L2 to
disconnect device line terminals.

7

Over-Current Protection

Select type and size of over-current
protection using Section 4-8 (fused
disconnect switch shown).

8

Receptacle (NEMA 6-50R)
Customer Supplied

Close and secure door on disconnect
device. Remove lockout/tagout device,
and place switch in the On position.

4

3

L1

L2

1

=GND/PE Earth Ground

2

1

5

6

7

Tools Needed:

L1

L2

240 VAC, 1

8