Performance data – nozzles, Heater parts from acf greenhouses – Modine Manufacturing GAS-FIRED HEATERS BD User Manual

Page 14

Advertising
background image

A choice of four air discharge nozzles
accommodate various heat throw
patterns illustrated. Equipped with
adjustable louver blades, nozzles are
fabricated from galvanized steel and
are offered either unpainted or
painted to match the finish of the
blower unit heaters. Nozzles are
flanged for easy attachment over
the air discharge opening of the
blower unit heater.

14

PERFORMANCE DATA – NOZZLES

Mounting Height, Heat Throw, Heat Spread (in feet)

S

S

H

S

T

T

H

S

S

40° DOWNWARD
NOZZLE

40° SPLITTER
NOZZLE

90° VERTICAL
NOZZLE

5-WAY
NOZZLES

Max. Mounting Ht. (ft.) H

16

20

21

24

26

25

27

29

31

32

32

Heat Throw (ft.) T

48

61

64

71

79

76

81

86

94

96

96

Heat Spread (ft.) S

16

20

21

24

26

25

27

29

31

32

32

Max. Mounting Ht. (ft.) H

14

22

23

24

26

26

24

29

31

32

32

Heat Spread (ft.) S

14

22

23

24

26

26

24

29

31

32

32

Max. Mounting Ht. (ft.) H

23

24

24

23

25

28

30

32

Heat Throw (ft.) T

56

60

59

59

62

70

75

80

Heat Spread (ft.) S

113

120

118

117

124

140

151

160

Max. Mounting Ht. (ft.) H

18

18

23

22

21

20

25

26

23

26

Heat Spread (ft.) S

25

26

32

31

29

28

35

36

32

36

BD 50

BD 75

BD 100

BD 125 BD 150

BD 175

BD 200

BD 250 BD 300 BD 350

BD 400

Model Number

40°

Downward

Nozzle

90° Vertical

Nozzle

40° Splitter

Nozzle

5-Way

Nozzle

Nozzle

Type

The above table is based on an inlet air temperature of 70°F and an air temperature rise of 55°F. Air deflectors on, 40° and 90° discharge nozzles set perpendicular to the
face of the air discharge opening. On 5-way nozzles all air deflectors set perpendicular to floor. Static pressure measured at 0.1" W.C. for 90° nozzle, 0.2" W.C. for 40°
downward and 5-way nozzle, and 0.3" W.C. for 40° splitter nozzle. Outlet velocities are approximately 1750 FPM for the 40° nozzles, 1000 FPM for the 90° nozzle and 1300
FPM for 5-way. For motor size, drive and blower rpm refer to pages 18 and 19. Mounting height measured from bottom of unit.

S

T

H

Heater Parts from ACF Greenhouses

Advertising