Miller Legend

4-3.

60 Hz Auxiliary Power Receptacles And Circuit Breakers

Ref. ST-168 046

5

7

8

1

2

9

3

4

6

Y

If unit does not have GFCI recep-
tacles, use GFCI-protected exten-
sion cord.

1

120 V 15 A AC Duplex Receptacle RC1

2

120 V 15 A AC Duplex Receptacle RC2

3

240 V 30 A Twistlock Receptacle RC3

Receptacles supply 60 Hz single-phase
power at power/idle speed only. Maximum
output from each duplex receptacle is is 2.5
kVA/kW. Maximum output from twistlock re-
ceptacle is 5 kVA/kW. For 60 Hz auxiliary
power, set controls as shown in table.

4

120 V 15 A AC Duplex GFCI Recep-
tacles GFCI1 And GFCI2 (Optional)

If a ground fault is detected, the GFCI recep-

tacle Reset button pops out and the circuit
opens to disconnect the faulty equipment.
Check for damaged tools, cords, plugs, etc.
connected to the receptacle. Press button to
reset receptacle and resume operation.

.

At least once a month, run engine at
power/idle speed and press Test button
to verify GFCI is working properly.

5

Circuit Breaker CB5

6

Circuit Breaker CB7

CB5 protects RC1 and CB7 protects RC2
from overload. If CB5 or CB7 opens, the re-
ceptacle does not work. Press button to re-
set breaker.

7

Circuit Breaker CB1

8

Circuit Breaker CB2

CB1 and CB2 protect all the 60 Hz recep-
tacles from overload. If CB1 or CB2 opens,
the 240 volt receptacle and one of the 120
volt receptacles does not work. 120 volts
may still be present at the 240 volt recep-
tacle. Press button to reset breaker.

9

Total Auxiliary Power Output

Combined output of receptacles limited to
the 5 kVA/kW output of the generator:

EXAMPLE: If 10 A is drawn from a 120 V du-
plex receptacle, only 16 A is available at the
240 V receptacle:

(120 V x 10 A) + (240 V x 16 A) = 5.0 kVA/kW

PANEL

ON

0

100

LOCK

UNLOCK

RUN/IDLE

RUN/IDLE

PANEL

ON

0

100

For 60 Hz

Auxiliary Power

While Welding

For 60 Hz

Auxiliary

Power Only