4-14. Connecting Input Power

Ref. 800 103-C / Ref. 802 295

3/8 in

3/8 in

Tools Needed:

!

Installation must meet all National

and Local Codes − have only quali-

fied persons make this installation.

!

Disconnect and lockout/tagout in-

put power before connecting input

conductors from unit.

!

Make input power connections to

the welding power source first.

!

Always connect green or green/yel-

low conductor to supply grounding

terminal first, and never to a line ter-

minal.

See rating label on unit and check input volt-

age available at site.
1

Input Power Conductors (Customer

Supplied Cord)

Select size and length of conductors using

Section 4-12. Conductors must comply with

national, state, and local electrical codes. If

applicable, use lugs of proper amperage

capacity and correct hole size.
Welding Power Source Input Power

Connections
2

Strain Relief

Route conductors (cord) through strain re-

lief and tighten screws.
3

Machine Grounding Terminal

4

Green Or Green/Yellow Grounding

Conductor

5

Reed Switch (Ground Current

Sensor) (Optional)

Connect green or green/yellow grounding

conductor to welding power source ground-

ing terminal first. If unit is equipped with op-

tional ground current sensor, route ground-

ing conductor through reed switch two

times and connect to grounding terminal.
6

Welding Power Source Line Terminals

7

Input Conductors L1 (U), L2 (V) And

L3 (W)

Connect input conductors L1 (U), L2 (V)

and L3 (W) to welding power source line ter-

minals.
Close and secure access door on welding

power source.
Disconnect Device Input Power Connec-

tions
8

Disconnect Device (switch shown in

OFF position)

9

Disconnect Device (Supply)

Grounding Terminal

Connect green or green/yellow grounding

conductor to disconnect device grounding

terminal first.
10 Disconnect Device Line Terminals
Connect input conductors L1 (U), L2 (V)

And L3 (W) to disconnect device line

terminals.
11 Overcurrent Protection
Select type and size of overcurrent protec-

tion using Section 4-12 (fused disconnect

switch shown).
Close and secure door on line disconnect

device. Remove lockout/tagout device, and

place switch in the On position.

= GND/PE Earth Ground

8

5

4

2

11

9

4

10

1

7

IMPORTANT

Input Terminal Board

L1 (U)

L3 (W)

L2 (V)

GND/ PE

3

4

7

6

Earth Ground

11/16 in