SECTION 3 – INSTALLATION

1

10 in (254 mm) Open Space
On Right Side And Rear Of
Unit For Good Airflow

2

Lifting Handle

Use handle to move unit.

3

Rating Label

Locate unit near correct input
power supply.

Right

Rear

1

3-1.

Selecting A Location

Ref. SA-145 666-C

2

3

1

Weld Output Cable

Determine total cable length in weld
circuit and maximum welding am-
peres. Use Section 3-3 to select
proper cable size.

Use shortest cables possible.

Do not use damaged cables.

2

Terminal Lug

Use lugs of proper amperage ca-
pacity and hole size for connecting
to work clamp, electrode holder, or
wire feeder.

3

Insulated Electrode Holder

Install according to manufacturer’s
instructions.

4

Work Clamp

Install onto work cable.

5

Dinse-Type Connector

Install onto weld cable.

10 ft (3 m)

Total Cable

Length In Weld

Circuit = 20 ft (6 m)

10 ft (3 m)

For Example,

sb6.2* 5/94 – S-0656

2

5

1

6

Tools Needed:

4

3

OR

3-2.

Selecting And Preparing Weld Output Cables

3-3.

Weld Cable Size*

Total Cable (Copper) Length In Weld Circuit Not Exceeding

100 ft (30 m) Or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Welding

Amperes

10 To 60%

Duty Cycle

60 Thru 100%

Duty Cycle

10 Thru 100% Duty Cycle

100

4

4

4

3

2

1

1/0

1/0

150

3

3

2

1

1/0

2/0

3/0

3/0

200

3

2

1

1/0

2/0

3/0

4/0

4/0

250

2

1

1/0

2/0

3/0

4/0

2-2/0

2-2/0

*Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least than 300 circular mils per ampere.