6. remote 14 socket information – Miller Electric 152 User Manual

Page 17

Advertising
background image

OM-206 Page 13

3-6.

Remote 14 Socket Information

A

+15 volts dc.

B

Contact closure to A completes +15 volts dc contactor control circuit.

C

Output command reference; 0 to +10 volts dc depending on setting of
Amperage Adjustment control R4.

D

Remote control circuit common.

E

Input command signal (potentiometer wiper or 0 to +10 volts dc).

K

Chassis common

Socket Information

Socket*

REMOTE 14

OUTPUT

(CONTACTOR)

AMPERAGE/

A/V

VOLTAGE

*The remaining sockets are not used.

Have only qualified persons make
this installation.

1

Line Disconnect Device Of
Proper Rating

2

230 Volts AC Wall Receptacle

3

Input Conductors

4

Grounding Conductor

Select size and length using Sec-
tion 3-8. Conductor rating must
comply with national, state, and
local electrical codes.

Install and connect input conduc-
tors and grounding conductor in
conduit or equivalent between wall
receptacle and deenergized line
disconnect device.

Connect grounding conductor first,
then line input conductors.

Be sure grounding conductor goes
to an earth ground.

5

Overcurrent Protection

Select type and size using Section
3-8. Install into deenergized line
disconnect device (fused discon-
nect switch shown).

6

Input Power Plug

Turn Off unit Power switch, and
connect plug to receptacle.

ssb2.2* 1/94 – ST-156 250-A

1

3

3

4

5

6

3

4

2

3-7.

Connecting Input Power To 152 Models

3-8.

Electrical Service Guide For 152 Ampere Models

Input Voltage

230

Input Amperes At Rated Output

27.1

Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes

40

Min Input Conductor Size In AWG/Kcmil

10

Max Recommended Input Conductor Length

In Feet (Meters)

167 (51)

Min Grounding Conductor Size In AWG/Kcmil

10

Reference: 1993 National Electrical Code (NEC).

S-0092J