INSTALLATION

FLUE OUTLET

Part No. Description

HE9 HE12 HE15 HE18

n/a

Maximum Flue Length (m)

4

4

4

4

201 180 Flue ext. 60/100

3

3

3

3

201 189 Terminal Vertical Roof 60/100

1

1

1

1

158 431 Weather Collar Pitched Roof

1

1

1

1

158 432 Weather Collar Flat Roof

1

1

1

1

201 182 90

o

Elbow Kit (60/100)

2

2

2

2

201 183 45

o

Elbow Kit (60/100)

2

2

2

2

201 867 Vertical Connector Kit

1

1

1

1

33 FLUE TERMINAL POSITION

610 mm

min.

ex7531

610 mm

min.

ex7532

The terminal should be positioned so that products of
combustion can safely disperse at all times.
Pluming may occur at the termination so, where
possible, terminal positions where this could cause a
nuisance should be avoided.
Minimum dimensions are shown below

Terminal Position

Minimum Dimension

Directly below an opening,

air brick, windows, etc.

300 mm

Below plastic / painted gutters

300 mm

Painted surface

300 mm

Below eaves or balcony

500 mm

mxhe7686

mxhe7687

34 FLUE ARRANGEMENT

Note.
The equivalent flue length resistance of the 90

o

elbow kit

(60/100) is 1.0m and the 45

o

elbow kit (60/100) is 0.75m.