Installation 2

2-12(Vol.2)

BASIC I/O AD TO BASIC I/O AD RS-422

Figure 2-6 RS-422 BASIC I/O AD-To-BASIC I/O AD

Figure 2-6 shows one individually shielded twisted pair of AWG 24. Each pair has a drain
wire connected to its shield. These drain wires are then connected to the signal grounds at
each unit. A separate shield encases the entire cable. The drain wire for the over-all shield is
tied to earth ground at one end. An example of acceptable wire for this application would be
Belden 8162. In a perfect world with no electrical noise and equal ground potentials
everywhere, the ground connection is not required. Omitting this signal ground in industrial
applications can lead to unstable operation and costly debugging

These connections are made by placing a 1/4 inch stripped wire into the openings of the wire
clamp terminal block and tightening the screw. This terminal block will accept gauges from
14 to 30 AWG. An alternate means of network connection is to use the ten pin male connector
located behind the clamp terminal block. This connector mates with Molex shell number 50-
57-9005, and uses pins 16-02-0103.

In addition to the BASIC I/O AD to BASIC I/O AD wiring, the installer should confirm that
the network type switches are set in their correct position: Multidrop, Repeater, or Last unit.