Co-linear vent installation – Jotul GF3 DVII User Manual

Page 10

Advertising
background image

Co-linear Vent Installation

The GF 3 DV Allagash may be vented through a
masonry or Class A prefabricated chimney using a
Co-linear Flexible Vent system approved for use with
a solid-fuel burning fireplace, When installed in the
manner described below, this system can improve
the performance of the appliance in cold climate
situations, as well as simplify the vent installation.
These guidelines must be followed:
1. Prior to the installation the chimney flue must be

thoroughly cleaned and inspected by a qualified
chimney service person.

2. In a masonry chimney, a fireclay liner must be

present the entire length of the chimney.

3. Prefabricated chimneys must be UL 103 or ULC S-

629 listed and have a minimum INSIDE diameter
of 6 inches, (150 mm).

4. No appliance can be installed into a chimney flue

serving any other appliance of any kind.

5. THE AIR INTAKE FLEX PIPE MUST EXTEND BEYOND

THE DAMPER AREA OF THE FIREPLACE.

6. If the intake flex does not extend the full length of

the chimney and connect to both the unit and the
termination cap, A METAL BLOCK OFF PLATE MUST
BE CONSTRUCTED AND INSTALLED ABOVE THE
UNIT PRIOR TO THE END OF THE INTAKE FLEX AND
MUST COMPLETELY SEAL THE CHIMNEY FLUE
FROM THE ROOM.

Consult with the local code authority having

jurisdiction before proceeding with this type of
installation.

Refer to the vent manufacturer’s instructions for

specific installation requirements.

WARNING: FAILURE TO POSITION THE PARTS AND

STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE MAY RESULT IN
PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE
TO MAINTAIN THE PROPER CLEARANCES TO COMBUS-
TIBLES AS DEFINED IN THIS MANUAL AND IN THE
INSTRUCTIONS PROVIDED WITH EACH VENT COMPO-
NENT.

FRESH AIR

EXHAUST

GAS

FIREPLACE

DAM PER AREA

Exhaust flex pipe

must extend the

entire length of the

chimney and

connected to a direct

vent termination

AIR INTAKE flex

pipe must be a

minimum of 6 ft.
(457 cm) and

extend beyond the

damper area

A metal block-

off plate must

completely seal

the chimney

from the room.

Fireclay liner must

exist through the

entire length of
the chimney

A DIRECT VENT

TERMINATION KIT

AND CAP IS

REQUIRED TO

ALLOW FRESH AIR

INTO THE CHIMNEY.

Figure 8. Co-linear Vent installed through
masonry
chimney.

Figure 8a. Co-linear Adaptor centerline.

24 3/4”

to center

of flue collar

28 3/4”

to top of

Co-linear

Adapter.

8

The Air Intake Flex
pipe must extend
beyond the
damper.