Johnson Controls Residential Gas TM9V MP User Manual

Page 35

Advertising
background image

438335-UIM-B-0509

Johnson Controls Unitary Products

35

DIAGNOSTIC FAULT CODE STORAGE AND

RETRIEVAL

The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even if power to the furnace
is lost. This feature should only be used by a qualified service tech-
nician.

If more than five error codes have occurred since the last reset, only the
five most recent will be retained. The furnace control board has a but-
ton, labeled LAST ERROR that is used to retrieve error codes. This
function will only work if there are no active thermostat signals. So any
call for heating, cooling or continuous fan must be terminated before
attempting to retrieve error codes.

To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED will
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.

If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.

FIGURE 42: Furnace Control Event Schedule

Thermostat Calling for Heat

Thermostat Satisfied

(Seconds)

THERMOSTAT

INDUCER

IGNITOR

MAIN VALVE

HUMIDIFIER

ELECTRONIC
AIR CLEANER

CIRCULATING
BLOWER

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

OFF

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

15
Sec.
Post
Purge

Fan on Delay
30 Seconds

0 2

17

22

52

0

60, 90, 120, 180 SEC.
Selectable Fan Off Delay