1 choice 1: display jbus settings, 2 choice 2: modify jbus settings, 3 choice 3: display jbus diagnostics – Schneider Electric 66123 User Manual

Page 73: 4 choice 4: reset jbus diagnostics

Advertising
background image

Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 73/98

Network Management Teleservice Card

APC by Schneider Electric

www.apc.com

10.1.3.1 Choice 1: Display Jbus settings

Enables reading of the card's Jbus settings

Jbus configuration :

Slave number : 7

Speed : 9600 bds

Data : 8 bits

stop bit : 1

Parity : None

10.1.3.2 Choice 2: Modify Jbus settings

Enables the modification of Jbus settings.

Setting Jbus configuration :

Set Slave number : 0x7

Set the Baud Rate [1: 38400, 2: 19200, 3: 9600, 4: 4800, 5: 2400, 6: 1200] :3

Set data format [1: 8 bits, 2: 7 bits] :1

Set stop bit [1: 1 bits, 2: 2 bits] :1

Set Parity [1: None, 2: Even, 3: Odd] :1

Wait during the new setting is saved ...

TLS/ Slave JBUS initialized

The Jbus configuration is now updated.

10.1.3.3 Choice 3: Display Jbus diagnostics

Enables reading of the Jbus diagnostics.

Jbus diagnostics :

Cpt1 - Bus Message Count:0

Cpt2 - CRC Error Count :0

Cpt3 - Slave Exception Error Count:0

Cpt4 - Slave Message Count:0

Cpt5 - Slave No Response Count:0

Cpt6 - Slave NAK Count:0

Cpt7 - Slave Busy Count:0

Cpt8 - Bus Caracter Overrun Count:0

Cpt9 - Slave Correct Response Count:0

10.1.3.4 Choice 4: Reset Jbus diagnostics

Reset the Jbus diagnostic counters.