Schneider Electric 66123 User Manual

Page 96

Advertising
background image

Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 96/98

Network Management Teleservice Card

APC by Schneider Electric

www.apc.com

11.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)

SNMP traps are sent when alarms appears and desappears.

Level : 1:informational , 2:major, 3:critical

MIB TRAP

Trap #

niveau

-upsmgBatteryFault (Nota1)

Trap 1

Level 3

-upsmgBatteryOK (Nota1)

Trap 2

Level 1

-upsmgAtLowBattery (Nota1)

Trap 5

Level 3

-upsmgFromLowBattery (Nota1)

Trap 6

Level 1

-upsmgChargerFault (Nota1)

Trap 7

Level 3

-upsmgChargerOK (Nota1)

Trap 8

Level 1

-upsmgOnBattery (Nota1)

Trap 11

Level 2

-upsmgReturnFromBattery (Nota1)

Trap 12

Level 1

-upsmgOnByPass

Trap 13

Level 2

-upsmgReturnFromByPass

Trap 14

Level 1

-upsmgUtilityFailure

Trap 17

Level 2

-upsmgUtilityRestored

Trap 18

Level 1

-upsmgOverLoad

Trap 21

Level 3

-upsmgLoadOK

Trap 22

Level 1

-upsmgOverTemperature (Nota1)

Trap 23

Level 3

-upsmgTemperatureOK (Nota1)

Trap 24

Level 1

-upsmgOffInProgress (Nota1)

Trap 31

Level 3

-upsmgCommunicationFailure

Trap 37

Level 3

-upsmgCommunicationRestored

Trap 38

Level 1

-upsmgRedundancyLost

Trap 65

Level 2

-upsmgRedundancyOK

Trap 66

Level 2

-upsmgProtectionLost

Trap 67

Level 2

-upsmgProtectionOK

Trap 68

Level 2

Nota1: This Information is not present with a Static Switch Cabinet unit.

If the Environment Sensor is detected , the following information are managed.:

- upsEnvironmentComFailure

Trap 53

Level 2

- upsEnvironmentComOK

Trap 54

Level 2

- upsEnvironmentTemperatureLow

Trap 55

Level 2

- upsEnvironmentTemperatureHigh

Trap 56

Level 2

- upsEnvironmentTemperatureOK

Trap 57

Level 2

- upsEnvironmentHumidityLow

Trap 58

Level 2

- upsEnvironmentHumidityHigh

Trap 59

Level 2

- upsEnvironmentHumidityOK

Trap 60

Level 2

- upsEnvironmentInput1Closed

Trap 61

Level 2

- upsEnvironmentInput1Open

Trap 62

Level 2

- upsEnvironmentInput2Open

Trap 64

Level 2

- upsEnvironmentInput2Closed

Trap 63

Level 2

The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified applications” page