Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

5

Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

ECO G 3 Way Outdoor Unit Specifications

ECO G 3 Way Heat Recovery VRF System

LPG option

The option of using LPG as a power supply increases flexibility
and avoids the problems of potential site restrictions in the
future. The purer fuel is also excellent for further reductions
in CO

2

emissions - a fact recognised by the government.

Still the only heat recovery (3 way) GHP system in

Europe.

The new M Series ECO G 3 Way offers even more

performance and outstanding features when you need

simultaneous heating and cooling. Now with increased

capacities available from 16HP to 25HP, SANYO offers the

greatest choice and flexibility to solve any power problem or

site requirement.

• Simultaneous heating and cooling for total control

• Reduced gas consumption by Miller-cycle engine

• Reduced electrical power consumption by using DC motors

• New lightweight design by use of aluminium engine block

reduces weight by 110kg

• Part load efficiencies increased

• Connectability increased to up to 36 indoor units

• Now available in 16, 20 and 25HP

• 200m maximum allowable piping length (L1) (equivalent - refer
to technical manual)

• Diversity ratio 50% - 130%

• Extended pipe runs (total 500m)

• Silent mode offers a further 2dB(A) reduction

• 10,000 run hours between engine service intervals (equivalent

to one maintenance every 3.2 years*)

• Full heating capacity down to -20°C

• No defrost cycle

* Assuming 3120 running hrs per year - 12 hrs x 5 days x 52 weeks

ECO G 3 Way is ideal for the following types of

application:

• Office buildings with a diverse range of room temperatures

due to differing load profiles.

• Buildings with computer rooms requiring year round cooling.

Additional parts

By taking its power supply from the nearest indoor unit, the
SANYO solenoid valve (change-over box) does not require any
additional fused spur and at only 150mm high can be easily
installed within a 200mm void space.

Dimensions ECO G 3 Way (16-25HP)

Comparison of the start times for heating operation

Room temperature (˚C )

Gas heat pump

Electric heat pump

Time axis (in case of the same load)

Outside air temperature (˚C)

Electric heat pump

Gas heat pump

Comparison of heating capacity

Heating capacity (% )

Comparison of the start times for heating operation

Room temperature (˚C )

Gas heat pump

Electric heat pump

Time axis (in case of the same load)

Outside air temperature (˚C)

Electric heat pump

Gas heat pump

Comparison of heating capacity

Heating capacity (% )

HP

16

20

25

Model

SGP-EZ150M2G2

SGP-EZ190M2G2

SGP-EZ240M2G2

Capacity

Cooling

kW

45.0

56.0

71.0

Heating

STD

kW

50.0

63.0

80.0

Heating Low temp*

53.0

67.0

75.0

Electricity

Cooling

kW

1.35

Heating

kW

1.01

1.54

Gas

Cooling

kW

31.6

38.3

60.9

Heating

STD

kW

36.1

43.0

58.0

Heating

LOW

47.3

56.4

64.9

COP

Cooling

1.37

1.41

1.14

Heating

1.35

1.43

1.34

AVE

1.36

1.42

1.24

Size

Height

mm

2,248

Width

1,800

Depth

1,000 (+60)

Weight

kg

845

875

Starter amperes

A

30

Piping

connection

Gas

Inches (mm)

1 1/8 (28.58)

Discharge

7/8 (22.22)

Liquid

3/4 (19.05)

Pipe fuel gas

R3/4 (bolt thread)

Pipe exhaust drain

mm

ø 25 rubber hose

Operation sound

dB(A)

57

58

62

Indoor/outdoor capacity ratio

50-180% *1

Number of indoor connections

36

* 1: Low temp condition: Outdoor temperature 2 C˚.

Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.

Please refer to tube sizing charts for pipe selections and pipe length parameters.

Rear View

Front View

Left Side View

at least 2000

Service Clearances for installation

(Units: mm)

Rear

(refrigerant tubing)

Rear

(refrigerant tubing)

at

le

as

t

60

0

at

le

as

t

60

0

at

le

as

t

10

00

at

le

as

t

10

00

at least

100

at least

100

at least

100

at least

350

at least

350

Front View

Front View

(Single-unit installation)

(Multi-unit series installation)

Suction refrigerant pipe

ш28.58

ш22.22

Size (mm)

Model Type

150

190 240

ш25.4

ш19.05

ш28

ш28

G: R3/4

ш20

4 - ш20

4 - ш24

OD: ø25 Length: 200

1

Discharge refrigerant pipe

2

Liquid refrigerant pipe

3

Exhaust gas drain hose

4

Inter-unit cable port

5

Electrical power supply port

6

Fuel gas port

7

Condensation drain opening

8

Rain and condensation outlet

9

Engine exhaust outlet

10

Suspension holes

11

Anchor holes

12

Segmented display

13

Coolant intake (top)

14

Vent

15

Top View

1800 (external)

22

48

(+

30

)

(1

81

)

400

10

14

(a

nc

ho

r p

itc

h)

1000

(anchor pitch)

10

14

12

13

1030 (suspension holes)

1000 (external)

ø736

1060 (frame width)

9

15

11

27

54

147

22

99

10

8

18

1

57

207

242

279

312

55

5

271

7

6

5

4

3
1
2

8