Eco g 2 way heat pump vrf system, Eco g 2 way outdoor unit specifications, Eco g w-multi for heat pump applications – Sanyo ECO G SGP-EZ190M2G2 User Manual

Page 4

Advertising
background image

6

Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

7

Rating Conditions: Cooling Indoor 27°C DB 19°C WB Outdoor 35°C DB 24°C WB Heating Indoor 20°C DB Outdoor 7°C DB 6°C WB

ECO G 2 Way Heat Pump VRF System

ECO G W-Multi for Heat Pump

Applications

The new and improved M Series heat pump

(2 Way) not only offers improved performance

but also increased flexibility. Now available as

multi-systems, many combinations are possible,

from 13HP to 50HP, allowing for more power

and enabling accurate matching of a system building

load. Additional new features include part load engine

management and compressor run hour equalisation.

• Reduced gas consumption by Miller-cycle engine

• Reduced electrical power consumption by using DC motors

• New lightweight design by use of aluminium engine block

reduces weight by 110kg

• Part load efficiencies increased

• Connectability increased - now up to 48 indoor units

• Multi-systems with combinations from 13HP up to 50HP

• 200m maximum allowable piping length (L1) (equivalent - refer
to technical manual)

• Diversity ratio 50-180%

• Extended pipe runs (total 500m)

• Industry leading sound levels

• Silent mode offers a further 2dB(A) reduction

• Chiller option

- 13HP (25kW cooling - 30kW heating)
- 25HP (56kW cooling - 67kW heating)

• 10,000 run hours between engine service intervals (equivalent

to one maintenance every 3.2 years*)

• Full heating capacity down to -20°C

• No defrost cycle

* Assuming 3120 running hrs per year - 12 hrs x 5 days x 52 weeks

ECO G 2 Way Outdoor Unit Specifications

Dimensions ECO G W-Multi 2 Way

HP

13

16

20

25

26

29

32

33*

36*

40*

45*

50

Model name

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW190M2G2W

SGP-EW240M2G2W

SGP-EW120M2G2W

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW190M2G2W

SGP-EW190M2G2W

SGP-EW240M2G2W

SGP-EW120M2G2W

SGP-EW150M2G2W

SGP-EW150M2G2W

SGP-EW190M2G2W

SGP-EW190M2G2W

SGP-EW190M2G2W

SGP-EW240M2G2W

SGP-EW240M2G2W

Capacity

Cooling

kW

35.50

45.00

56.00

71.00

80.50

90.00

91.50

101.00

112..0

127.00

142.00

Heating

STD

kW

40.00

50.00

63.00

80.00

90.00

100.00

103.00

113.00

126.00

143.00

160.00

Heating Low temp*1

42.50

53.00

67.00

75.00

85.00

95.50

106.00

109.50

120.00

134.00

142.00

150.00

Hot water

12.00

16.00

20.00

25.00

24.00

28.00

32.00

32.00

36.00

40.00

45.00

50.00

Electricity

Cooling

kW

0.85

1.35

1.70

2.20

2.70

2.20

2.70

Heating

1.01

1.54

2.02

2.55

3.08

Gas consumption

Cooling

kW

24.50

31.60

38.30

60.90

49.00

56.10

63.20

62.80

69.90

76.60

99.20

121.80

Heating

STD

kW

28.10

36.10

43.00

58.00

56.20

64.20

72.20

71.10

79.10

86.00

101.00

116.00

Heating

LOW

36.80

47.30

56.40

64.90

73.60

84.10

94.60

93.20

103.70

112.80

121.30

129.80

COP

Cooling

1.40

1.37

1.41

1.14

1.40

1.38

1.37

1.41

1.39

1.41

1.25

1.14

Heating

1.37

1.35

1.43

1.34

1.37

1.36

1.35

1.41

1.39

1.43

1.38

1.34

AVE

1.39

1.36

1.42

1.24

1.39

1.37

1.36

1.41

1.39

1.42

1.31

1.24

Max COP (inc hot water) Cooling

1.87

1.85

1.92

1.54

1.87

1.86

1.85

1.90

1.89

1.92

1.69

1.54

Size

Height

mm

2,248

Width

1,800

1,800 + 100 (min distance) + 1,800 (in a straight installation)

Depth

1,000 (+60)

Weight

kg

790

820

850

1,580

1,610

1,640

1,670

1,700

Starter amperes

(A)

30

Piping connection

Gas

Inches (mm)

1 1/8 (28.58)

1 3/8 (34.92)

1 5/8 (41.27)

Liquid

1/2 (12.7)

5/8 (15.88)

3/4 (19.05)

Balance

3/8 (9.52)

Pipe fuel gas

R3/4 (bolt thread)

Pipe exhaust drain

ø25 rubber hose

Operation sound

dB(A)

57

58

62

60

61

63

65

Indoor/outdoor capacity ratio

50-180 %

50-130 %

Number of indoor connections

32

36

48

* In case of these combinations EGW190M2G2W is able to connect as W-multi instead of EW190M2G2w.

* 1: Low temp condition: Outdoor temperature 2 C˚.

Condenser actual pipe connections may vary from above pipe connections shown, please refer to technical manuals for full details.

Please refer to tube sizing charts for pipe selections and pipe length parameters.

Capacity Hot Water is available when outside ambient air temperature is above 7C˚.

Rear View

Front View

Left Side View

at least 2000

Service Clearances for installation

(Units: mm)

Rear

(refrigerant tubing)

Rear

(refrigerant tubing)

at

le

as

t

60

0

at

le

as

t

60

0

at

le

as

t

10

00

at

le

as

t

10

00

at least

100

at least

100

at least

100

at least

350

at least

350

Front View

Front View

(Single-unit installation)

(Multi-unit series installation)

Gas refrigerant pipe (Gas tube)

ш25.4

ш28.58

ш12.7

Size (mm)

120

Model Type

150

190 and 240

ш15.88

ш9.52

ш28

ш28

ш28

G: R3/4

ш20

4 - ш20

4 - ш24

Rp3/4

Rp3/4

OD: ø25 Length: 200

1

Liquid refrigerant pipe (Liquid tube)

2

Refrigerant balance pipe (Balance tube)

3

Exhaust gas drain hose

4

Electrical power supply port

5

Inter-unit cable port

6

Fuel gas port

7

Condensation drain opening

8

Rain and condensation outlet

9

Engine exhaust outlet

10

Suspension holes

11

Anchor holes

12

Segmented display

13

Coolant intake (top)

14

Vent

15

Hot water intake

16

Hot water outlet

17

Cable inlet for interlock and the like

18

Top View

1800

22

48

400

10

14

(a

nc

ho

r p

itc

h)

1000

(anchor pitch)

10

14

12

12

1040

1000

ш736

1060

9

15

11

27

11

8

50

55

54

147

207

242

275

312

461

55

83

99

95

22

55

5

16

3

271

3

17

16

7

2

1

4

8

18

6

5