Installing – Sun Microsystems Sun Fire X4100 M2 User Manual

Page 10

Advertising
background image

2

Sun Fire X4100/X4100 M2 and X4200/X4200 M2 Servers Installation Guide • May 2007

5. Configure the preinstalled Solaris™ operating system or install a supported

operating system of your choice. For details, refer to one of the following:

■

“Configuring the Preinstalled Solaris 10 Operating System” on page 36

■

Sun Fire X4100/X4100 M2 and X4200/X4200 M2 Servers Operating System
Installation Guide
, 819-1158

■

Sun Fire X4100/X4100 M2 and X4200/X4200 M2 Servers Windows Operating
System Installation Guide
, 819-4346

6. Customize your server as needed. For details, refer to the “System Management”

section of the online information system or the Integrated Lights-Out Manager
Administration Guide
, 820-0280-10.

Installing the Server Into a Rack With
Optional Slide Rails

To install your server in a four-post rack using the orderable slide-rail option, follow
these procedures. These slide-rails are compatible with a wide range of equipment
racks that meet the following standards:

■

Four-post structure (mounting at both front and rear). Two-post racks are not
compatible.

■

Rack horizontal opening and unit vertical pitch conforming to ANSI/EIA
310-D-1992 or IEC 60927 standards.

■

Distance between front and rear mounting planes between 610 mm and 915 mm
(24 inches to 36 inches).

■

Clearance depth (to front cabinet door) in front of front rack mounting plane at
least 25.4 mm (1 inch).

■

Clearance depth (to rear cabinet door) behind front rack mounting plane at least
800 mm (31.5 inches) or 700 mm (27.5 inches) without cable management arm.

■

Clearance width (between structural supports and cable troughs) between front
and rear mounting planes at least 456 mm (18 inches).

Note –

Although the Sun Fire X4100/X4100 M2 server is pictured in the illustrations

in this section, these procedures also apply to the Sun Fire X4200/X4200 M2 server.

Caution –

Always load equipment into a rack from the bottom up so that it will not

become top-heavy and tip over. Deploy your rack’s anti-tilt bar to prevent the rack
from tipping during equipment installation.