Maintenance

To remove the eliminator, stand inside the access panel and lift with two
hands on an eliminator section, this will indicate where one section stops
and another starts. Lift the eliminators at that intersection, removing two
packs at one time (see image). Once the first two packs are removed,
the remaining packs should be easily removed. Pay close attention to the
orientation and placement, they are not symmetrical. Each pack should
be replaced at the location which it was removed. Repeat this process for
the second half of the tower.

Proper eliminator pack replacement is essential to tower operation.
Incorrect installation may result in excessive drift rates and fan inef-
ficiency! To ensure packs are reinstalled in the correct orientation,
it is recommended that one pack is left in its original location inside
the tower as a reminder of pack orientation. Place packs in the tower
in the order they were removed. Packs should nest tightly with each
other, leaving a level surface with no gaps. The last two packs should
be installed at the same time. Place the final two packs according
to the image above, and push down to complete.

Note