Installation

Motor Wiring

Wire motor leads as shown on the motor nameplate matching the supply
voltage. Do not deviate from the motor nameplate wiring.
Either of following symbols may be shown on the motor nameplate –
Δ, Δ Δ

,

Y

, or

YY

. These symbols represent how the motor is constructed on

the inside and in no way have anything to do with a Delta or Wye electrical
distribution system serving the motor.

When using a starter:

• Set motor overload protection to 110% of motor nameplate amps.

This setting allows the fan motor to operate during cooler weather.
During cooler weather it is common for the motor to draw 6 to
10% higher than nameplate amps. High amps are common during
tower commissioning when the tower is dry and the ambient air
temperature is cool.

• Do not start the motor more than

six times per hour. Short cycling

the tower will cause fuses, breakers or O.L.s to operate and will
decrease motor life.

When using a two-speed starter:

• Motor rotation must be the same at slow speed and high speed.
• Single winding motor requires a starter with a shorting contactor.
• Two-winding motor requires a starter with out a shorting contac-

tor.

• All two-speed starters must have a 20 second time delay relay

when switching from high speed to low speed.

• Do not start the motor more than

six times per hour (each low

speed start and each high speed start count as one start).

When using a VFD:

Before beginning, ensure that the motor is rated for “Inverter Duty”
per NEMA MG-1, part 31.

• Set the VFD solid state overload protection to 119% of motor

nameplate amps and set “maximum current parameter” in the
VFD to motor nameplate amps. “Maximum current parameter” will
reduce fan speed and limit amp draw to nameplate amps during
cold weather operation. If furnished with a mechanical O.L. set this
at 110% over motor nameplate amps.

• Motor rotation must be the same in both VFD mode and By-pass

mode.

Note