8 Exhaust System

4.1

Planning

Carefully plan the generator exhaust system to ensure a
safe, quiet installation.

Verify that the installation

complies with all state and local requirements and
applicable articles of the codes listed at the beginning of
this manual.

4.2

Clearance Requirements

Kohler Co. recommends a minimum clearance of
38 mm (1 1/2 in.) between the exhaust system parts
and the fuel system, the electrical system, and all
combustible components to protect the generator set
components and to avoid igniting adjacent combustible
materials.

4.3

Exhaust Piping, If Used

Route the exhaust piping to maintain minimum
clearances and to minimize exhaust piping bends. Use
a tail pipe as short as possible with as few bends as
possible to reduce back pressure. Design the exhaust
piping to prevent excessive back pressure of the
unit-mounted muffler, if equipped. See Figure 4-1 for
the allowable exhaust back pressure. Do not apply
weight or pressure to the unit-mounted muffler,
otherwise premature exhaust-system damage will
occur.

Adding exhaust-pipe extensions

to the

unit-mounted muffler may cause excessive vibration
and noise transmitted to the vehicle.

For generator sets without a unit-mounted muffler,
install a muffler made of aluminized steel or other
corrosion-resistant material of welded or crimped
construction.

Model

Allowable Exhaust

Back Pressure

10/13/15ERG

< 10.2 kPa (3.0 in. Hg)

Figure 4-1 Allowable Exhaust Back Pressure