Port number, Connect mode, Table 7-3. flow control options – Lantronix UDS1100 User Manual

Page 43: Table 7-4. reserved port numbers

Advertising
background image

7: Setup Mode: Channel Configuration

UDS1100 User Guide

43

Use the following table to select flow control options:

Table 7-3. Flow Control Options

Flow Control Option

Hex

No flow control

00

XON/XOFF flow control

01

Hardware handshake with RTS/CTS lines 02

XON/XOFF pass characters to host

05

Port Number

The setting represents the source port number in TCP connections. It is the number
that identifies the channel for remote initiating connections.

Port No (10001) ? _

The default setting for Port 1 is 10001. The range is 1-65535, except for the following
reserved port numbers:

Table 7-4. Reserved Port Numbers

Warning:

We recommend that you not use the reserved port numbers

for this setting as incorrect operation may result.

Use Port 0 for the outgoing local port to change with each connection. The port range
is 50,000-59,999. Each subsequent connection increments the number by 1 (it wraps
back around to 50,000).

Only use this automatic port increment feature to initiate a connection using TCP. Set
the port to a non-zero value when the unit is in a passive mode or when using UDP
instead of TCP.

Connect Mode

Connect Mode defines how the unit makes a connection, and how it reacts to
incoming connections over the network.

ConnectMode (C0) ? _

Enter Connect Mode options in hexadecimal notation. The default setting is C0.

Note:

All bit positions in the table that are blank represent “don’t care” bits for

that particular option, which can be set to either a 0 or 1 value.

Port Numbers Reserved for

1 – 1024

Reserved (well known ports)

9999

Telnet setup

14000-14009

Reserved for Redirector

30704 Reserved

(77F0h)

30718 Reserved

(77FEh)

Advertising