Specifications 15

Figure 14 Front view of the (4) 70-250 A circuit breaker panel

The DC output connections can accommodate two 4/0 cables back to back for each circuit breaker.

The required lugs can be either for two 3/8” holes at 1” c-c or for two 1/2” holes at 1-3/4” c-c.
Refer to Table 21 for the maximum panel capacity.

The (4) 70-250 A circuit breaker panel can accept up to:

• four breakers (70 to 225 A) mid trip with or without the metering shunt option (1 pole breakers)
• two breakers (70 to 225 A) mid trip with the relay trip option (takes a 2 pole space)
• two breakers (250 A) mid trip with or without the metering shunt option (takes a two pole

breaker)

• one (250 A) breaker mid trip with the relay trip option (takes a 3 pole space)

Table 18

Circuit breaker sizes available for the (4) 70-250 A circuit breaker panel

Nominal current

CPC

70 A (no shunt)

A0617079

70 A (with shunt)

A0617080

70 A (with relay trip)

A0617081

100 A (no shunt)

A0616667

100 A (with shunt)

A0616668

100 A (with relay trip)

A0616669

150 A (no shunt)

A0616670

150 A (with shunt)

A0616671

150 A (with relay trip)

A0616672

200 A (no shunt)

A0616673

200 A (with shunt)

A0616674

200 A (with relay trip)

A0616675

225 A (no shunt)

A0605489

225 A (with shunt)

A0605490

225 A (with relay trip)

A0605492

250 A (no shunt)

A0616676

250 A (with shunt)

A0616677

250 A (with relay trip)

A0616678

900A MAX. PANEL CAPACITY

1

2

3

4

CIRCUIT BREAKER PANEL

NT6C12EE

FA

REL ( )

SER NO ( )

UNIT

AMPS

LOAD

225

225

225

225

1

2

3

4

(4) 70-250 A