2 helios rectifiers 200i/48 and 200e/48, Helios rectifiers 200i/48 and 200e/48, Table 25 – Liebert 1500 User Manual

Page 28: Table 26

Advertising
background image

22 Specifications

Electrical specifications of the Helios Rectifier 100/48

The electrical specifications of the Helios Rectifier 100/48 are listed in Table 25.

3.7.2

Helios Rectifiers 200I/48 and 200E/48

Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48

The mechanical specifications of the Helios Rectifier 200I/48 and 200E/48 are listed in Table 26.

Table 25

Electrical specifications of the Helios Rectifier 100/48

Parameter

Specification

Input voltage:

208/240 V AC, 1-phase, 47-63 Hz
Input voltage range: 176 to 264 V AC

Input current:

31 A nominal at 208 V AC input and -56 V DC, 100 A output

Recommended AC
service input:

50 A, two pole AC circuit breaker

Output voltage:

Float: -48 to -58 V DC
Equalize: 0 to 4 V DC above Float
Maximum: -59.5 V DC

Output current:

100 A per rectifier
100 A for a one position shelf
300 A for a three position shelf

Input protection:

A two pole / 45 A circuit breaker opens both lines.

Output protection:

The rectifier is protected by a 120 A circuit breaker at the output. The output current
is limited to a value adjustable from 50% to 105% of the rated capacity of the
rectifier. This circuit is factory set to 105 A.

Output regulation:

The rectifier output voltage is automatically regulated to remain within ±0.5% of the
selected value under all load conditions and within the specified input voltage,
frequency, and ambient temperature ranges. And within + 1% for any combinations
of specified input, output and environmental conditions.

Efficiency:

Efficiency is better than 88% at a nominal input voltage of 208/240 V AC and an
output load greater than 40 A.

Power factor:

Power factor is 0.99 at a nominal input voltage of 208 V AC and output loads greater
than 40 A.

Electromagnetic
interference (EMI):

The rectifier meets the FCC requirements for conducted and radiated EMI for Class
“A” equipment.

Heat dissipation:

763 W (2606 Btu/hr)

Table 26

Mechanical specifications of the Helios Rectifiers 200I/48 and 200E/48

Figure

Height

Depth

Width

Weight

Figure 22

254 mm

(10 in.)

559 mm

(22 in.)

521 mm

(20.5 in.)

42.3 kg

(93 lb)

Advertising