4 externally mounted battery return busbar, Externally mounted battery return busbar, Table 22 – Liebert 1500 User Manual

Page 24: Mechanical specifications of a single lamination

Advertising
background image

18 Specifications

3.4

Externally Mounted Battery Return Busbar

The battery return busbar is designed to mount on the overhead racking for 6000 A systems and

top cabled 1500, 3000 or 4000 A power systems. It can also be mounted on a wall or on the floor

below the raised floor for bottom cabled 1500, 3000 or 4000 A power systems (which are assumed

to be installed on a raised, computer type floor).

3.4.1

Mechanical Specifications of the External Battery Return Busbar

The external battery return busbar kit consists of a group of single busbar laminations and

attachment hardware assembled as shown in Figure 17 (6000 A shown). The kit can grow verti-

cally in such a way as to maintain the 3-ft maximum radius grounding requirement. Laminations

are added as required to increase the capacity. The mechanical specifications of a single lamina-

tion are listed in Table 22.

Figure 17 Top and side views of the external battery return busbar

3.4.2

Electrical Specifications of the External Battery Return Busbar

A single busbar lamination has a current carrying capacity of 3000 A.

Table 22

Mechanical specifications of a single lamination

Figure

Length

Width

Thickness

Figure 17

863.6 mm

(34 inches)

152.4 mm
(6 inches)

12.7 mm

(0.5 inches)

NOTE
All bars and details are 0.5 in. thick.
* For a 1500 A system, only the bottom level is provided for the external

battery return ground bar.

Top view of the external ground bar

Side view of the external ground bar installed on

auxiliary framing above the power system

Smaller busbar for
small wires and cables

Future growth as required

Available

configurations:

= 1500* &
3000 A

= 4000 A

= 6000 A

34” (864 mm)

6” (152 mm)

6”

Advertising