Maintenance 39

5.2

Troubleshooting

Table 39 provides a list of the problems that may occur on the Helios DC System 4000/48, along

with their possible causes. Blown fuses and tripped circuit breakers should always be investi-

gated before utilizing Table 39.

Table 39

Fault diagnosis

Fault symptom

Possible causes

No DC output current

Open AC circuit breaker
Open DC circuit breaker
Faulty connection between the power shelf and the rectifier (Helios
Rectifier 100/48)
Faulty connection between the rectifier and the power plant
Sense leads opened

Incorrect indication of the DC
output current

Incorrect meter calibration
Loose shunt leads connection

Low float voltage

Faulty rectifier(s)
Shorted battery cell(s)
Prolonged power failure
Incorrect float voltage adjustment
Sense leads opened

Low recharge voltage

Incorrect float voltage adjustment
Discharge load greater than the rectifier’s capacity (batteries are
recharging or the system is in manual bypass)
Sense leads opened

High float or recharge voltage

Faulty rectifier(s)
Incorrect Float/Equalize adjustment

Failure to generate alarms
during alarm conditions

Incorrect connections between the controller and the rectifiers and
distribution panels

Failure to generate cabinet
alarm during minor or major
alarm conditions

Faulty LP fuse on the controller (F31)
Faulty cabinet alarm lamp
Faulty or loose connection

Failure to generate RFA alarm
under appropriate conditions

Faulty rectifier
Faulty wiring
Faulty RFA LED

Failure to generate FA alarm

Faulty wiring
Faulty fuse
Faulty FA LED
Loose connection

HV lamp lit

High discharge voltage condition
Incorrect HV level adjustment

LV lamp lit

Low discharge voltage condition
Incorrect LV level adjustment

HF lamp lit

High discharge voltage condition
Incorrect HF level adjustment

LF lamp lit

Low discharge voltage condition
Incorrect LF level adjustment

FA lamp lit

Blown fuse or extended FA alarm

CFA lamp lit

Blown charge fuse

DFA lamp lit

Blown distribution fuse

RECT MIN lamp lit

One rectifier has failed

RECT MAJ lamp lit

Two or more rectifiers have failed

RECT FAN lamp lit

Defective rectifier fan(s)