16 Specifications

Figure 15 Front view of the (2) 400 A circuit breaker panel

The DC output connections can accommodate two 750 MCM cables back to back for each circuit

breaker. The required lugs must be for two 1/2” holes at 1-3/4” c-c.
Refer to Table 21 for the maximum panel capacity.

The panel accepts up to:

• two breakers (400 A) mid trip with or without the metering shunt option
• one breaker (400 A) mid trip with the relay trip option (takes a 3 pole space)

Figure 16 Front view of the (1) 600-700 A circuit breaker panel

The DC output connections can accommodate four 750 MCM cables back to back. The lugs must

be for two 1/2” bolts at 1-3/4” c-c.
Refer to Table 21 for the available circuit breakers and the maximum panel capacity.

Table 19

Circuit breaker kits available for the (2) 400 A circuit breaker panel

Nominal current

CPC

400 A (no shunt)

P0748316

400 A (with shunt)

P0748317

2 x 400 A (no shunt)

P0748318

2 x 400 A (with shunt)

P0748319

400 A (with relay trip)

P0748320

Table 20

Circuit breaker kits available for the (1) 600-700 A circuit breaker panel

Nominal current

CPC

600 A (no shunt)

P0875700

600 A (e/w shunt)

P0875701

600 A (e/w relay trip)

P0875702

900A MAX. PANEL CAPACITY

1

2

CIRCUIT BREAKER PANEL

NT6C12EF

FA

REL ( )

SER NO ( )

UNIT

AMPS

LOAD

400

400

1

2

(2) 400 A

900A MAX. PANEL CAPACITY

1

2

CIRCUIT BREAKER PANEL

NT6C12EG

FA

REL ( )

SER NO ( )

UNIT

AMPS

LOAD

600

1

(1) 600-700 A