Operation 35

4.4

Rectifiers

The rectifiers provide isolated, filtered and regulated DC power, from either a single-phase AC

source (Helios Rectifier 100/48) or a three-phase AC source (Helios Rectifier 200I/48 or 200E/48),

for charging a positive grounded battery.
The nominal output is adjustable over the range of -46 to -59.5 V to float a 23 or 24 cell battery

string.
The rectifiers are equipped with AC input and DC output circuit breakers, a digital ammeter,

potentiometers for the adjustment of thresholds, and LED indicators for alarm indications.
The rectifiers use high frequency switching technology and forced air-cooling.
Refer to the appropriate rectifier user manual listed in 6.0 - Reference Documents for detailed

operation information on the Helios Rectifier 100/48, the Helios Rectifier 200I/48, or the Helios

Rectifier 200E/48.

4.5

AC Junction Box

The AC junction box is part of the rectifier cabinet used for the Helios Rectifier 200E/48. It is

located at the top of the cabinet for top fed systems, or at the bottom of the cabinet for bottom fed

systems.
The AC junction box provides AC connection interface for up to six rectifiers and facilitates the

addition and/or replacement of rectifiers in a working system. The AC supply from the AC service

panel is hard wired inside the box at the time of the initial installation. Detailed cabling and con-

necting guidelines for the AC junction box can be found in 5.0 - Maintenance.
The rectifiers are provided with a factory-installed AC cord equipped with a male connector. This

male connector is plugged into a matching female receptacle at the rear of the AC junction box.

For the complete procedures for adding or replacing a rectifier, refer to 5.0 - Maintenance. Note

that caps are provided to protect the unused female receptacles.

4.6

Distribution Panels

All distribution panels provide local alarm indication on the panel itself, and alarm extension to

the controller for additional indication on the controller and the cabinet and further extension to

remote alarm facilities.

4.7

Terminating Assemblies (Optional)

Terminating assemblies are optional devices used to facilitate the connecting of loads to distribu-

tion fuses or circuit breakers larger than 199 A. These assemblies can be used in top fed systems

only (they cannot be used on bottom fed systems). Each terminating assembly provides connection

facilities for up to six loads without having to route the cables inside the cabinet during installa-

tion.
Two terminating assemblies can be used on an auxiliary distribution cabinet, while only one ter-

minating assembly can be used on a main control and distribution cabinet.

!

WARNING
PREVENTING ELECTRICAL SHOCKS
WHEN OPENING THE DOOR OR WIRING THE AC INPUT OF

THE RECTIFIERS INSIDE THE JUNCTION BOX, ENSURE THAT

THE ASSOCIATED AC BREAKERS, LOCATED IN THE AC

SERVICE PANEL, ARE IN THE OFF POSITION AND THAT A

WARNING TAG CLEARLY INDICATES THAT THESE BREAKERS

ARE TO REMAIN OFF UNTIL THE AC WIRING HAS BEEN

COMPLETED. DO NOT INSERT FUSES, OR OPERATE CIRCUIT

BREAKER OR SWITCHES TO ON UNTIL THE WIRING IS

COMPLETED AND YOU ARE INSTRUCTED TO DO SO.