Caution – Lennox International Inc. o23v User Manual

Page 15

Advertising
background image

Page 15

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

(All Air Through Ventilated Attic)

NOTE−The inlet and outlet air openings shall each have a free area of at
least one square inch (6.4 square centimeters) per 4,000 Btu (1172 W)
per hour of the total input rating of all equipment in the enclosure.

CHIMNEY

OR OIL

VENT

WATER

HEATER

OUTLET

AIR

VENTILATION LOUVERS

(Each end of attic)

INLET AIR

(Ends 12" above

bottom)

FIGURE 12

OIL

FURNACE

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

OUTLET AIR

INLET AIR

WATER

HEATER

CHIMNEY

OR OIL

VENT

FIGURE 13

NOTE−Each air duct opening shall have a free area of at least one
square inch (6.4 square centimeters) per 2,000 Btu (586 W) per hour
of the total input rating of all equipment in the enclosure. If the equip-
ment room is located against an outside wall and the air openings
communicate directly with the outdoors, each opening shall have a
free area of at least one square inch (6.4 square centimeters) per
4,000 Btu (1172 W) per hour of the total input rating of all other equip-
ment in the enclosure.

OIL

FURNACE

When ducts are used, they shall be of the same cross−sec-
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3" (76 mm). In calculating free area, the
blocking effect of louvers, grilles, or screens must be con-
sidered. If the design and free area of protective covering is
not known for calculating the size opening required, it may
be assumed that wood louvers will have 20 to 25 per-
cent free area and metal louvers and grilles will have 60
to 75 percent free area. Louvers and grilles must be
fixed in the open position or interlocked with the equip-
ment so that they are opened automatically during equip-
ment operation.

CAUTION

Combustion air openings in the front of the furnace
must be kept free of obstructions. Any obstruction
will cause improper burner operation and may result
in a fire hazard or injury.

CAUTION

The barometric shall be in the same atmospheric
pressure zone as the combustion air inlet to the
furnace. Deviation from this practice will cause
improper burner operation and may result in a fire
hazard or injury.

Direct Connection of Outdoor Air for Combustion

The Beckett AFII burner was designed to allow for direct air
intake piping (4" [102 mm]). The maximum equivalent
length of pipe is 70 feet (21.3 m). A 90

_ elbow equals 6

feet (1.8 m).

To convert the AFII burner from confined space to out-
side combustion air, simply remove the three screws at-
taching the inlet air scoop to the burner and insert 4"
(102 mm) direct air intake piping.

The use of a barometric relief placed in the intake pipe is
recommended when outdoor combustion air is directly
connected to the burner. This will allow confined space
air to be used as combustion air in the event that the
opening to the outdoor air becomes blocked. Using a
barometric relief in the intake will reduce the chance of
sooting.

CAUTION

DO NOT USE a barometric draft relief in exhaust
vent pipe if outdoor combustion air is connected
directly to the burner. The only exception are baro-
metric draft reliefs as required by FIELD or TJERN-
LUND power vents.

Removal of Unit from Common Venting System

In the event that an existing furnace is removed from a venting
system commonly run with separate appliances, the venting
system is likely to be too large to properly vent the remaining
attached appliances. The following test should be conducted
while each appliance is in operation and the other ap-
pliances not in operation remain connected to the com-
mon venting system. If venting system has been installed
improperly, the system must be corrected as outlined in the
previous section.

Advertising