Troubleshooting: Burner starts and fires, but short cycles (too little heat)
Source
Procedure
Causes
Correction
Thermostat
Check thermostat.
Heat anticipator set too low
Correct heat anticipator setting.
Vibration at thermostat
Correct source of vibration.
Thermostat in the path of a warm air
draft
Shield thermostat from draft or relocate.
Limit Control
Connect voltmeter between
line voltage connections to
Dirty furnace air filters
Clean or replace filter.
line voltage connections to
primary control (black &
white leads). If burner
Burner running too slow
Increase blower speed to maintain proper
temp. rise.
white leads). If burner
cycles due to power
interruption it is cycling on
Blower motor seized or burned out
Replace motor.
interruption, it is cycling on
limit.
Blower bearings seized
Replace bearings and shaft.
limit.
Blower wheel dirty
Clean blower wheel.
Blower wheel in backward
Reverse blower wheel.
Wrong motor rotation
Replace with properly rotating wheel.
Restrictions in return or supply air
system
Correct cause of restriction.
Adjustable limit control set too low
Reset limit to maximum stop setting.
Power
If voltage fluctuates, fault is
in the power source.
Loose wiring connection
Locate and secure connection.
in the power source.
Recheck voltage at the
power source.
Low or fluctuating line voltage
Call power company.
Troubleshooting: Burner starts and fires, but loses flame and lock out on safety
Source
Procedure
Causes
Correction
Poor Fire
After burner fires,
immediately jumper
Unbalanced fire
Replace nozzle
immediately jumper
across flame detector
terminals at the primary
Too much air − − lean short fire
Reduce combustion air − check combustion.
terminals at the primary
control.
S
If burner continues to
Too little air − − long dirty fire
Increase combustion air − check combustion.
S
If burner continues to
run (does not lock out
of safety) fault may be
Excessive draft
Adjust barometric damper for correct draft.
of safety), fault may be
poor fire. Inspect fire.
Too little draft or restriction
Correct draft or remove restriction.
Flame Detector
S
If fire is good, check for
Dirty CAD cell face
Clean CAD cell face.
g
,
fault in flame detector
circuit.
Faulty CAD cell − − exceeds 15000
hms
Replace CAD cell.
Loose or defective cad cell wires
Secure connections or replace cad cell holder
and wire leads.
Pump loses prime − air slug
Prime pump at bleed port
Oil Supply
S
If burner loses flame
(does not lock out on
Pump loses prime − air leak in
supply line
Check supply line for loose connections and
tighten fittings.
(does not lock out on
safety), fault is in the
fuel system.
Water slug in line
Check oil tank for water (over 1 inch) pump or
drain out water.
Partially plugged nozzle or nozzle
strainer
Replace nozzle.
Listen for pump whine
Restriction in oil line
Clear restriction.
Plugged fuel pump strainer
Clean strainer or replace pump.
Cold oil − outdoor tank
Change to number 1 oil.