Lennox International Inc. o23v User Manual

Page 29

Advertising
background image

Page 29

Troubleshooting: Burner starts and fires, but short cycles (too little heat)

Source

Procedure

Causes

Correction

Thermostat

Check thermostat.

Heat anticipator set too low

Correct heat anticipator setting.

Vibration at thermostat

Correct source of vibration.

Thermostat in the path of a warm air
draft

Shield thermostat from draft or relocate.

Limit Control

Connect voltmeter between
line voltage connections to

Dirty furnace air filters

Clean or replace filter.

line voltage connections to
primary control (black &
white leads). If burner

Burner running too slow

Increase blower speed to maintain proper
temp. rise.

white leads). If burner
cycles due to power
interruption it is cycling on

Blower motor seized or burned out

Replace motor.

interruption, it is cycling on
limit.

Blower bearings seized

Replace bearings and shaft.

limit.

Blower wheel dirty

Clean blower wheel.

Blower wheel in backward

Reverse blower wheel.

Wrong motor rotation

Replace with properly rotating wheel.

Restrictions in return or supply air
system

Correct cause of restriction.

Adjustable limit control set too low

Reset limit to maximum stop setting.

Power

If voltage fluctuates, fault is
in the power source.

Loose wiring connection

Locate and secure connection.

in the power source.
Recheck voltage at the
power source.

Low or fluctuating line voltage

Call power company.

Troubleshooting: Burner starts and fires, but loses flame and lock out on safety

Source

Procedure

Causes

Correction

Poor Fire

After burner fires,
immediately jumper

Unbalanced fire

Replace nozzle

immediately jumper
across flame detector
terminals at the primary

Too much air − − lean short fire

Reduce combustion air − check combustion.

terminals at the primary
control.

S

If burner continues to

Too little air − − long dirty fire

Increase combustion air − check combustion.

S

If burner continues to
run (does not lock out
of safety) fault may be

Excessive draft

Adjust barometric damper for correct draft.

of safety), fault may be
poor fire. Inspect fire.

Too little draft or restriction

Correct draft or remove restriction.

Flame Detector

S

If fire is good, check for

Dirty CAD cell face

Clean CAD cell face.

g

,

fault in flame detector
circuit.

Faulty CAD cell − − exceeds 15000
hms

Replace CAD cell.

Loose or defective cad cell wires

Secure connections or replace cad cell holder
and wire leads.

Pump loses prime − air slug

Prime pump at bleed port

Oil Supply

S

If burner loses flame
(does not lock out on

Pump loses prime − air leak in
supply line

Check supply line for loose connections and
tighten fittings.

(does not lock out on
safety), fault is in the
fuel system.

Water slug in line

Check oil tank for water (over 1 inch) pump or
drain out water.

Partially plugged nozzle or nozzle
strainer

Replace nozzle.

Listen for pump whine

Restriction in oil line

Clear restriction.

Plugged fuel pump strainer

Clean strainer or replace pump.

Cold oil − outdoor tank

Change to number 1 oil.