Troubleshooting: fan board operating sequence, Troubleshooting: burner fails to start – Lennox International Inc. o23v User Manual

Page 26

Advertising
background image

Page 26

Troubleshooting: Fan board operating sequence

Action

System Response

Thermostat calls for heat.
(W terminal is energized.)

Blower control board closes oil primary control T−3T connections.

Ignition system and oil primary control start the furnace. Oil flows as long as oil primary control
senses flame.

Burner motor energized and heat fan on delay timing begins. When timing is complete, the
circulating fan is energized at heat speed and warm air is delivered to the controlled space.

Thermostat ends call for heat.
(W terminal is de−energized.)

Oil primary control is de−energized, terminating the burner cycle.

Heat fan off delay timing begins. When timing is complete, circulating fan is de−energized.

Blower control board returns to standby mode (oil primary control and circulating fan are off).

Burner fails to light.

Oil primary control locks out within lockout timing (timing depends on oil primary control).

Burner motor is de−energized.

Established flame fails.

Burner motor is de−energized and oil primary control goes into recycle mode.

If the fan off delay is longer than the recycle timing, the heat fan continues to run through the
next trial for ignition.

Limit switch opens.

Oil primary control shut off the burner.

Circulating fan is energized immediately.

A15 control board opens oil primary control T−3T connections.

Circulating fan runs as long as limit stays open.

Limit switch closes.

If there is a heat demand, A15 control board energizes oil primary control, initiating burner light
off.

Troubleshooting: Burner fails to start

Source

Procedure

Causes

Correction

Thermostat

Check thermostat settings.

Thermostat in OFF or
COOL

Switch to HEAT.

Thermostat is set too low

Turn thermostat to higher temperature.

Safety
Overloads

Check burner motor,
primary safety control, &
auxiliary limit switch

Burner motor overload
tripped

Push reset button pump motor.

auxiliary limit switch.

Primary control tripped on
safety

Reset primary control.

Auxiliary limit switch tripped
on safety

Reset auxiliary limit.

Power

Check furnace disconnect
switch & main disconnect

Open switch

Close switch.

switch & main disconnect.

Blown fuse or tripped circuit
breaker

Replace fuse or reset circuit breaker.

Thermostat

Touch jumper wire across
thermostat terminals on
primary control If burner

Broken or loose thermostat
wires

Repair or replace wires.

primary control. If burner
starts, then fault is in the
thermostat circuit.

Loose thermostat screw
connection

Tighten connection.

thermostat circuit.

Dirty thermostat contacts

Clean contacts.

Thermostat not level

Level thermostat.

Faulty thermostat

Replace thermostat.

CAD Cell

Disconnect the flame
detector wires at the
primary control If the

Flame detector leads are
shorted

Separate leads.

primary control. If the
burner starts, fault is in the
detector circuit.

Flame detector exposed to
light

Seal off false source of light.

detector circuit.

short circuit in the flame
detector

Replace detector.

table continued on next page