Specifications / optional accessories – Lennox International Inc. o23v User Manual

Page 2

Advertising
background image

Page 2

SPECIFICATIONS

Oil
H

ti

Model Number

O23V2/3−70/90

O23V3/4−105/120

O23V5−140/154

Heating
Performance

Low Fire

Input − Btuh (kW)

70,000 (20.5)

105,000 (30.8)

140,000 (41.0)

Performance

Output − Btuh (kW)

58,000 (16.7)

85,000 (24.9)

113,000 (33.1)

High Fire

Input

90,000 (26.4)

119,000 (34.8)

154,000 (45.1)

g

Output

74,000 (21.7)

97,000 (24.9)

125,000 (36.6)

1

A.F.U.E.

83%

81%

81%

Flue Connection Round − in. (mm)

6 (152)

6 (152)

6 (152)

Temperature Rise Range °F (°C)

50 − 80 (28 − 44)

50 − 80 (28 − 44)

55 − 85 (31 − 47)

Oil Burner

Nozzle rating − gph (L/hr) − Low

.50 (1.9)

.65 (2.5)

.85 (3.2)

4

High

4

.65 (2.5)

4

.75 (2.8)

4

1.00 (3.8)

Nozzle spray angle − Low

80

° hollow

80

° solid

80

° solid

4

High

80

° solid

80

° solid

80

° solid

Oil Burner Pump

1 Stage

1 Stage

1 Stage

Oil Burner Pump Pressure − psig (Pa)

100 (690)

140 (965)

140 (965)

Oil Burner Air Inlet Connection (dia.) − in (mm)

4 (102)

4 (102)

4 (102)

Blower
Data

Motor hp (W)

1/2 (373)

1/2 (373)

3/4 (560)

Data

Wheel nom. diameter x width − in. (mm) 10 x 8 (254 x 203)

10 x 10 (254 x 254)

12 x 11 (305 x 280)

Nominal add−on cooling − Tons (kW)

1.5 − 3 (5.3 − 10.6)

2 − 3.5 (7.0 − 12.3)

3 − 5 (10.6 − 17.6)

2

Filter

Number of filters

1

1

3

2

Size of filters − in.

16 x 25 x 1

16 x 25 x 1

16 x 25 x 1

mm

406 x 635 x 25

406 x 635 x 25

406 x 635 x 25

Shipping weight Ċ lbs. (kg) 1 package

225 (102)

225 (102)

275 (125)

Electrical

Characteristics

120V−60hz−1ph

120V−60hz−1ph

120V−60hz−1ph

Maximum overcurrent protection (amps)

15

15

15

Optional Accessories − Must Be Ordered Extra

Half−Height Coil Case

19M11

19M11

19M12

g

Fits uncased C33 coils

B"−width

B"−width

C"−width

Dimensions − in.

5 x 19−1/2 x 21−3/4

5 x 19−1/2 x 21−3/4

5 x 22−1/2 x 22−7/8

mm

127 x 495 x 552

127 x 495 x 552

127 x 572 x 581

Oil Filters

10 micron without mounting bracket

81P89

81P89

81P89

10 micron with mounting bracket

53P92

53P92

53P92

Replacement cartridge − 10 micron, 45 gph

53P93

53P93

53P93

Filter restriction indicator gauge

53P90

53P90

53P90

SignatureStat

t Home Comfort Control

81M27

81M27

81M27

Two Stage Oil Pump

65A44

65A44

65A44

1

Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations. Isolated combustion system rating for non−weatherized furnaces.

2

Cleanable frame type filters. Furnished with unit in Side Filter Adaptor Kit for field installation external to the cabinet.

3

Requires return air from both sides of cabinet.

4

Nozzle must be field provided for field conversion to higher heating input.

Advertising