4 thresholds in the web interface, 1 temperature/humidity sensor thresholds, 2 dry-contact sensor thresholds – Liebert EM User Manual

Page 19: Thresholds in the web interface, Temperature/humidity sensor thresholds, Dry-contact sensor thresholds, Table 7, Table 8

Advertising
background image

Web Interface Overview

13

4.4

Thresholds in the Web Interface

The OpenComms EM collects data from connected sensors at regular intervals. When a reading

crosses a user-defined threshold:

• The sensor’s status changes.
• Alerts are sent—if the unit is configured for e-mail, pager or SNMP trap alerts.

4.4.1 Temperature/Humidity Sensor Thresholds

Temperature and humidity sensors have four thresholds: High Critical, High Warning, Low Warning

and Low Critical. The Normal range is determined by these limits. Table 7 shows examples of limits

for these types of sensors. Each level is color-coded in the Web interface for easy identification.

Using the examples of temperature sensor limits in Table 7, the following is a typical scenario:

• The temperature of a monitored area rises to 90°F. The status changes at two points:

• The status changes to High Warning when the temperature reaches 75°F. The name of the

sensor, the current reading and the status are displayed in yellow text in the Web interface.

• As the temperature continues to rise, the status changes to High Critical at 85°F (displayed

in red text).

• At each change in status, the unit sends alerts if it is configured to do so.

• When the temperature falls to 74°F, the status changes to Normal (displayed in green text) and a

return-to-normal alert is sent if the unit is configured to send alerts.

• When a sensor is disconnected from the unit, its status changes to Not Present (black text) and

the sensor’s name appears in gray text.

4.4.2 Dry-Contact Sensor Thresholds

A dry-contact sensor has only two states: Normal and Critical, as shown in Table 8. The user

defines Normal as either Normally Open or Normally Closed and the OpenComms EM designates the

opposite state as Critical.

Using the examples for a dry-contact sensor in Table 8, the following is a typical scenario:

• The sensor’s normal state is defined as Normally Open.
• When the contact closes, the sensor’s status changes to Critical (displayed in red text). The unit

sends alerts, if it is configured to do so.

• When the state changes again (the contact opens), the sensor’s status changes to Normal (dis-

played in green text) and a return-to-normal alert is sent if the unit is configured to send alerts.

Table 7

Examples of sensor limits - temperature and humidity sensors

Limit

Examples of Limits

Text Display Color

Graph

Line

Color

Temperature

(°F)

Humidity

(% RH)

Sensor

Name

Status &

Current Value

High Critical

85

55

Red

Red

Red

High Warning

75

50

Yellow

Yellow

Yellow

Low Warning

65

30

Yellow

Yellow

Yellow

Low Critical

60

25

Red

Red

Red

Other conditions
Normal

66°F to 74°F

31% to 49%

Green

Green

Not Present

(sensor is not connected)

Gray

Black

Table 8

Examples of sensor limits - temperature and humidity sensors

Limit

Example of

User-Defined State

Text Display Color

Graph

Line

Color

Sensor

Name

Status &

Current Value

Critical

Closed

Red

Red

Red

Other conditions
Normal

Normally Open

Green

Green

Not Present

(sensor is not connected)

Gray

Black