Pinout Guides

38

6.0

P

INOUT

G

UIDES

6.1

Modem Setup and Pinout Guide

The OpenComms EM must be connected to a modem to send pager alerts when a sensor reading

crosses a user-defined threshold (see 5.5.2 - Modem Setup for more information).
The unit is compatible with modems that have DB9 or DB25 serial COM ports. A proper cable must

be constructed to allow communication between the unit and the modem. This cable connects the

RJ45 connector labeled Modem on the back of the unit to the serial port on the modem.
Refer to Table 13 for a pinout guide for building the correct cable. For more information on construct-

ing this type of cable, call Liebert Monitoring Application Support at 1-800-222-5877 or contact your

local Liebert representative.

6.2

Contact Closure Cable Pinout Guide

All OpenComms EM models can

accommodate a contact closure cable in

either sensor port. Contact closure cables

are available separately from Liebert in

various lengths (see Table 3).
To make your own contact closure cable,

refer to Table 14 for the pinout for this

cable.

• Pin 2 is the contact that may be

defined as either Normally Open or

Normally Closed.

• Pins 6 and 8 must be tied together to

form the common.

6.3

Serial Cable Pinout Guide (EM PDU & vEM-14 Controllers)

The serial cable included with

OpenComms EM PDU and vEM-14 con-

trollers is designed for connecting the

OpenComms EM unit to an MP

Advanced power strip.
To make your own cable, refer to

Table 15 for the pinout for this cable.

Table 13

OpenComms EM to DCE modem pinout guide

RJ45 Pin # Signal Name

Description

DB25 Pin # DB9 Pin #

1

DTR

Data Term Ready

20

4

2

CTS

Clear to Send

5

8

3

GND

Signal Ground

7

5

4

TXD

Transmit Data

2

3

5

RXD

Receive Data

3

2

6

CD

Carrier Detect

8

1

7

RTS

Request to Send

4

7

8

DSR

Data Set Ready

6

6

Table 14

Contact closure cable pinout

OpenComms EM RJ45

Dry-Contact Device

1

2

Normally Open or Normally Closed

3

4

5

6

Common - tied to Pin 8

7

8

Common - tied to Pin 6

Table 15

Serial cable pinout - MP Advanced Power Strip

OpenComms EM RJ45

MP Advanced power strip

1

8

2

3

3

2

4

5

5

4

6

Not Connected

7

Not Connected

8

1