5.5.2 Modem Setup

The OpenComms EM may be configured to send a numeric message to a pager.
Note: The unit requires an external modem to send pager alerts. The modem port is set at 9600 baud,

no parity, 8 data bits and 1 stop bit. For details on connecting the unit to a modem, see 6.1 - Modem

Setup and Pinout Guide and 2.3.3 - Connect to a Modem.
To generate automatic pager alerts when a sensor reading crosses a threshold, log in (see 5.1 - Open

the Web Interface and Log In) and:

• Click on the Alerts tab at the top of the Web interface, as shown below.

• Click on the Modem link on the left side of the window. The right side of the window displays

setup information for pager alerts, as shown above.

• The Call on Error box allows you to enable or disable pager alerts. Click on the Down arrow to the

right of the box and select Yes to activate or No to de-activate pager alerts.

• If needed, enter numbers in the Access/Country Code box as follows:

• Enter any numbers needed to access an outside line—for example, 9—where the call is being

placed.

• If dialing from outside the U.S., enter the country code of the location where the call is being

placed.

• Enter numbers to be dialed to reach the pager:

• Area Code - Enter the area code of the pager to be dialed.
• Phone Number - Enter the pager phone number (the number may be entered with or without

spaces or hyphens).

• The Message Delay box allows you to specify the amount of time to wait after a connection is

established before dialing begins. Click on the Down arrow to the right of the box and select from

the list: 5, 10, 15, 20 or 30 seconds.

• Click on one of the Dial Using buttons—Tone or Pulse—to indicate the type of connection where

the call is being placed.

• The Resend box, on the left side of the window, allows you to specify whether the unit will con-

tinue to dial the pager at certain intervals as long as the monitored area is in a warning or critical

state. Click on the Down arrow to the right of the Resend box and select Never or a time interval:

15 or 30 seconds, 1, 5, 10, 15 or 30 minutes or 1 hour.
Note: The unit will stop attempting pager alerts as soon as it detects a normal state.

• Click the Test button to send a test pager message.
• Click on the Apply button to keep your changes. (Or click Reset to cancel the changes.)

Modem

link

Activate pager

alerts

Wait before

dialing

Pager number

to be dialed

Type of

dialing

Resend

Optional access #s

or country code

Send a test

pager alert