Lennox Hearth MODEL MONTAGE 32FS User Manual

Page 7

Advertising
background image

7

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

In addition to the standard installation instructions, the following instruc-

tions may be required by local, state or federal building codes:

• Installation should be in accordance with the Manufactured Home and

Safety Standard (HUD), CFR 3280, Part 24.

• The stove must be permanently bolted to the floor using two or three

1/4" or 5/16" diameter x 5" lag screws as shown in Figures 4A, 4B, 5A

and 5B.

• Connecting the Montage™ 32FS stove to outside combustion air is

required in manufactured home installations and when required by local

building codes. An outside air inlet must be provided for combustion

and be unrestricted while unit is in use. Use a galvanized or stainless

steel pipe for the duct (the outside air inlet on the stove is 1-5/8”

diameter). The air intake on the exterior of the home should always

be located a minimum of 18" below the flue termination (see Figures

4B and 15). The Inlet shall remain free of obstruction while unit is in

operation and constructed in a manner so as to prevent material from

dropping into the inlet or into the area beneath the dwelling. The inlet

shall also have a screen with openings not larger than 1/4" to prevent

rodents from entering.

• Stove must be permanently electrically grounded to the steel chassis

of the manufactured home using a 8 GA copper wire and a serrated

or star washer (to penetrate paint or protective coating to ensure

grounding). The location selected for ground attachment to the stove

must be dedicated for this purpose. Grounding must comply with

NFPA-70-latest edition standards, CSA C22.1-latest edition in Canada,

as well as any local codes.

• See Pages 9 through 15 for additional information on venting require-

ments.

WARNING: DO NOT INSTALL THIS STOVE IN A SLEEPING ROOM IN

A MANUFACTURED HOME.

CAUTION: THE STRUCTURAL INTEGRITY OF THE MANUFACTURED

HOME FLOOR, WALLS, CEILING/ROOF MUST BE MAINTAINED.

Figure 4A - Manufactured Home Installation

Manufactured Home Exhaust Vent Pipe Installation Guidelines

This stove is approved for venting with Type L and Type PL pellet vent pipe
listed to UL 641 and ULC S609. We recommend the use of venting products
manufactured by Security Chimneys International. The pipe should extend

at least 3 feet above the part of the roof through which it passes. The top

of the pipe should be at least 2 feet above the highest required elevation

of any part of the manufactured home within 10 feet of the pipe (see Page

12, Manufactured Home Chimney Height Requirements).

If the exhaust vent exits the manufactured home at a location other than

the roof, and exits at a point 7 feet or less above the ground level on which

the manufactured home is position a guard or method of enclosing the

pipe shall be provided at the point of exit for a height of up to 7 feet. The

openings, if any, in this guard shall not allow a 3/4” rod to pass through.

A 1/2” rod could pass through but should not be able to touch the pipe

when inserted through the opening a distance of 4 inches.

Chassis

Floor

Bolt

Floor

Protector

MANUFACTURED HOME INSTALLATION

Bolt

Figure 4B - Manufactured Home Installation

Outside

Air Inlet

Holes for lag screws when securing to manufactured home floor

Options:

1) Install one lag screw in the front center hole and one in the rear

center hole.

OR

2) Install one lag screw in the front center hole and two in the rear

side holes.

Open front

glass door and

remove ash

pan to access

front lag screw

hole.