Panel model number guide, Lcp128, Lcp) (120 v only) – Lutron Electronics LCP128 User Manual

Page 2

Advertising
background image

R

2

Installation Guide for Dimming and Switching Panels

Panel Model Number Guide

LCP128

TM

(LCP) (120 V

only)

See page 5 for 230/220-240 V

Modules:
Quantity and Type

Prefix

Example

L C P - 2 X 2 D 1 A 4 T - 1 2 0 4 M L - 2 0

Prefix

LCP = LCP dimming panel

Module Types

_X _S _D _Q _A _M _F _T

List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.

X = Four-Circuit Switching (Relay) (XP)
S = One-Circuit Dimming (1U)
D = Two-Circuit Dimming (2U)
Q = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM

Ballast Control (TVM)

Feed Voltage

120 for 120 V

Feed
Voltage

Branch Circuit
Breaker Rating

Feed
Type

Feed Type/Input Ratings

FT = Feed-through panel (circuit breakers not included) /

120 V

3ML = 1 phase 3 wire feed (split phase) / 120/240 V
4ML = 3 phase 4 wire feed / 120/208 V

Branch Circuit Breaker Rating

Omit for feed-through panels
20 for 20 A branch circuit breakers

Frequency - All Model Numbers and Voltages
50/60 Hz

Output (Load) Ratings

Module Type Rating
XP

16 A per circuit

1U, 2U, 4U

16 A per module

4A

16 A per module, 10 A per output

4M

16 A per module, 5 A per output
(1/4 HP motor),
1 motor per output

4FSQ

2 A per output (single ceiling fan)

TVM

50 mA per channel, 750 mA per system

Module Quantity Limits

Panel Size

Feed type

TVM

4A

4U

4M

Mini

Feed-through

NA

Any combination up to 3 modules

Mini

Feed-through

0-4

Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Mini

Breakers

NA

Any combination up to 3 modules

Mini

Breakers

0-4

Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules

Standard

Feed-through

NA

Any combination up to 9 modules

Standard

Feed-through

0-12

Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Standard

Breakers (main lugs)

NA

Any combination up to 9 modules

Standard

Breakers (main lugs)

NA

Any combination up to 7 modules

Standard

Breakers (main lugs)

0-12

Any combination up to 7 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules

Standard

Breakers (main lugs)

0-12

Any combination up to 5 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Notes

• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready

XP

0
0

0

0