Installation Guide for Dimming and Switching Panels 5

Panel Model Number Guide

(continued)

Prefix

CCP = Custom combination panel

Module Types

_X _L _E _A _M _T

List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.

X = Four-Circuit Switching (Relay) (XP)
L = Four-Circuit Dimming (4U)
E = Four-Circuit Electronic Low Voltage Dimming (4E)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
T = 0-10 V, DALI (broadcast), DSI, and PWM

Ballast Control (TVM)

Feed Voltage
230 = 230 V

(CE)

240 = 220-240 V

(non-CE)

Feed Type
FT = feed-through panel (circuit breakers not included)
4IS = 3 phase 4 wire isolation switch
2M = 1 phase 2 wire input breakers (mini only)
4M = 3 phase 4 wire input breakers (mini only)

GRAFIK Systems

TM

(CCP/LCP) (230/220-240 V

only)

Modules:
Quantity and
Type

Prefix

Example

C C P - 1 X 4 L 2 T - 2 3 0 4 I S - C E - L C P - C G P _ _ _

Feed
Voltage

Feed
Type

Custom
Panel Suffix
(contact Lutron for custom options)

Region
Suffix

Region Suffix
CE = 230 V
AU = 220-240 V
Note: Should match feed voltage

Controller Type
Omit for single-link circuit selector
2L = 2Link

TM

circuit selector

LCP = LCP128

Custom Panel Suffix (optional)
Indicates panel with special options

Frequency
(All Model Numbers and Voltages)

50/60 Hz

Output (Load) Ratings
Module Type Rating
XP

16 A per circuit

4U (230 V

) 13 A per module, 10 A per output

4U (240 V

) 16 A per module

4A

13 A per module, 8 A per output

4E

16 A per module, 10 A per output

4M

16 A per module, 5 A per output
(1/4 HP motor), 1 motor per output

TVM

50 mA per channel, 750 mA per system

Controller
Type

Module Quantity Limits

Panel Size

Feed type

TVM

4A

4U

4E

4M

Mini

Feed-through

NA

Any combination up to 3 modules

Mini

Feed-through

0-4

Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Mini

Input breakers

NA

Any combination up to 3 modules

Mini

Input breakers

0-4

Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules

Standard

Feed-through

0-12

Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Standard

Input breakers

0-12

Any combination up to 8 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules

Standard

Input breakers

0-12

Any combination up to 6 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Notes

• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready

XP

0
0

0