Panel Model Number Guide

(continued)

Prefix

CCP = Custom combination panel

Module Types

_X _L _A _M _F _T

List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.

X = Four-Circuit Switching (Relay) (XP)
L = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM

Ballast Control (TVM)

Feed Voltage

120 for 120 V

GRAFIK Systems

TM

(CCP) (120 V

only)

Example

C C P - 2 X 2 L 1 A 4 T - 1 2 0 4 M L - 2 0 - C G P _ _ _

Module Quantity Limits

Panel Size

Feed type

TVM

4A

4U

4M

Mini

Feed-through

NA

Any combination up to 3 modules

Mini

Feed-through

0-4

Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Mini

Breakers

NA

Any combination up to 3 modules

Mini

Breakers

0-4

Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules

Standard

Feed-through

NA

Any combination up to 9 modules

Standard

Feed-through

0-12

Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Standard

Breakers (main lugs)

NA

Any combination up to 9 modules

Standard

Breakers (main lugs)

NA

Any combination up to 7 modules

Standard

Breakers (main lugs)

0-12

Any combination up to 8 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules

Standard

Breakers (main lugs)

0-12

Any combination up to 5 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules

Notes

• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready

XP

0
0

0

0

Modules:
Quantity and Type

Prefix

Feed
Voltage

Feed
Type

Custom
Panel Suffix
(contact Lutron for custom options)

Branch
Circuit
Breaker
Rating

Feed Type / Input Ratings

FT = feed-through panel (circuit breakers not included) /

120 V

3ML = 1 phase 3 wire feed (split phase) / 120/240 V
4ML = 3 phase 4 wire feed / 120/208 V
2 = 1 phase 2 wire input breakers (mini only)
3 = 1 phase 3 wire input breakers (mini only)
4 = 3 phase 4 wire input breakers (mini only)

Branch Circuit Breaker Rating

20 = 20 A branch circuit breakers
15 = 15 A branch circuit breakers

Custom Panel Suffix (optional)
Indicates panel with special options

Frequency
(All Model Numbers and Voltages): 50/60 Hz

Output (Load) Ratings
Module Type Rating
XP, 4U

16 A per circuit

4A

16 A per module, 10 A per output

4M

16 A per module, 5 A per output
(1/4 HP motor)

4FSQ

2 A per output (single ceiling fan)

TVM

50 mA per channel, 750 mA per system