Panel mounting – Lutron Electronics LCP128 User Manual

Page 8

Advertising
background image

R

8

Installation Guide for Dimming and Switching Panels

Panel Mounting

Mounting Guidelines

• For Indoor Use Only! NEMA, Type 1 enclosure, IP20.
• Panel generates heat. Mount only where ambient

temperature is 32-104 °F (0-40 °C).

• Relative humidity must be < 90% non-condensing.
• Reinforce wall structure for panel weight and local

codes; see table.

• Allow 12 in. (305 mm) clearance above and below

panel.

• Mount within 7° of true vertical.
• Mount panel where audible noise is acceptable.

(Internal relays click.)

• Mount panel so line (mains) voltage wiring is at least

6 ft. (1.8 m) from audio or electronic equipment and
associated wiring.

• Install in accordance with all national and local

electrical codes.

1
2
3
4
5
6
7
8
9

Max. Weight w/o

Packaging

Pounds (kg)

No.

Modules

Max. Heat

BTUs (Kcal)/Hr.

Surface Mounting

• Lutron recommends using 1/4 in. (6 mm)

mounting bolts (maximum size accepted by
keyholes).

• Reinforce wall structure as required for weight and

local codes.

• Do not mount panel directly to wall board/drywall.

Recess Mounting

• Mount to wall stud by screwing through slots in

corners of panel.

• Mount panel between flush and 1/8 in. (3 mm)

below finished wall surface.

Side View:

Surface Mount

Side View:

Recess Mount

Front View

Recommended Mounting Heights*
(for LCP128 systems)
Mini

45 in. (1143 mm)

Standard

25 in. (635 mm)

* Measure from floor to bottom of panel;

optimal viewing height for controller.

1

2

4

3

5

6

8

7

A

B
C
N

Load circuit wiring

Feed wiring

Do not
obstruct
vents!

PELV
(Class 2: USA)
Wiring

Air flow

Air flow

Low-
voltage
control
wiring for
TVM loads

90 (22.68)

170 (42.84)
250 (63.00)
330 (83.16)
410 (103.32)
490 (123.48)
570 (143.64)
650 (163.80)
730 (183.96)

24 (11)
35 (16)
37 (17)
68 (25)
71 (26)
74 (27)
77 (28)
80 (29)
83 (30)

C

Ca

au

uttiio

on

n!! 230 V

panels with 13 A circuit

breakers are intended for industrial or
commercial use only.

C

Ca

au

uttiio

on

n!! This equipment is air-cooled. Vents

must not be blocked or you will void the
warranty.

LP8/32-1204ML-20 shown