0 installation and configuration, 1 install the main cabinet, 1 tower ups installation – Liebert GXT2-6000RT230 User Manual

Page 14: 2 rack-mount ups installation, Nstallation, Onfiguration, Install the main cabinet, Tower ups installation, Rack-mount ups installation, Figure 5

Advertising
background image

Installation and Configuration

10

5.0

I

NSTALLATION

AND

C

ONFIGURATION

Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until

instructed to do so in 6.0 - Initial Start-Up and Electrical Checks.
Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer

or Liebert representative.

Install the GXT2 indoors in a controlled environment, where it cannot be accidentally turned off.

Place it where air flows unrestricted around the unit. The installation location must be free of water,

flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of

100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to

40°C (32 -104°F).

5.1

Install the Main Cabinet

The GXT2 may be installed in either a tower configuration or in a rack, depending on available space

and use considerations. Determine the type of installation and follow the appropriate instructions in

either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.

5.1.1 Tower UPS Installation

When using the GXT2 in a tower configuration, use the included support base (shown below, left) to

stabilize the UPS. If any external battery cabinets are added, they will include spacers to accommo-

date the additional cabinets (shown below, right).

Figure 5

Tower-use support bases, spacers for external battery cabinets

5.1.2 Rack-Mount UPS Installation

When using the GXT2 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed

rails or a shelf.
When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The fig-

ures accompanying 5.1.3 - Installing the Adjustable Rack-Mount Kit—Sold Separately shows

the positioning of the rack-mounting brackets. Liebert recommends taking the internal batteries out

of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.

!

CAUTION

The UPS is heavy (see 13.0 - Specifications). Take proper precautions

when lifting or moving it.

NOTE
UPS operation in sustained temperatures above 25°C (77°F) reduces battery life.
This device is intended for use in an Installation Category II environment.

!

CAUTION

Only three (3) M4 screws are used on the side of the GXT2 where the Power Distribution Box

is located. The fourth mounting hole is above the Power Distribution Box and is not used.

3U

2U

2U

5U support base for GXT2

End bases and 3U spacer

3U

2U

2U

Spacers added to support base

to accommodate additional battery cabinets

3U