Specifications

32

13.0 S

PECIFICATIONS

Table 7

UPS specifications

Model Number

GXT2-6000RT230

GXT2-4500RT230

Model Rating

6KVA / 4,200W

4.5KVA / 3,150W

Dimensions mm (in.)

Unit, W x D x H

221 x 547 x 430 (8.7 x 21.5 x 16.9)

Shipping, W x D x H

560 x 690 x 500 (22.05 x 27.17 x 19.7)

Weight kg (lbs)

Unit

67 (151)

67 (151)

Shipping

79.5 (175.3)

79.5 (175.3)

Input AC Parameters

Nominal Operating Frequency

50 or 60Hz (Factory Default = 50)

Factory Default VAC

230VAC

User Configurable VAC

220/230/240VAC

(May be modified using configuration program)

Operating Voltage Range Without

Battery Operation

176 – 276VAC

Maximum Allowable VAC

276VAC

Input Frequency Without Battery

Operation

40 - 70Hz

Input Power Connection

PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)

Output AC Parameters

Factory Default VAC

230VAC

Output Connections

PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)

Frequency

50Hz or 60Hz, Nominal

Waveform

Sinewave

Main Mode

Overload

>200% for 96 milliseconds; 131 - 199% for 2 seconds;

112- 129% for 10 seconds with transfer to bypass

Battery Parameters

Type

Valve-regulated, non-spillable, lead acid

Quantity x V

20 x 12V

Battery Mfr. / Part #

Yuasa / REW 28-12

Back-up Time

See Table 6 - Battery run times

Recharge Time (Internal Batteries)

3 hrs. to 90% capacity after full discharge into 100% load

Bypass Protection Limits

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

Disable Bypass operation

When the input frequency prevents synchronous operation

Environmental

Operating Temperature

0

°C to +40°C (+32°F to +104° F)

Storage Temperature

-15

°C to +50°C (+5°F to +122° F)

Relative Humidity

0-95% non-condensing

Operating Elevation

Up to 2000m (6600 ft) at 40

°C (104° F) without derating

15,000m (50,000 ft.) maximum

Storage Elevation

Audible Noise

<55 dBA, at 1 meter from the rear

<50 dBA, at 1 meter from the front or sides

Agency

Safety

EN62040-1-1; TUV/GS

EMI/EMC/C-Tick EMC

EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive

ESD

EN61000-4-2, Level 4, Criteria A

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

Electrical Fast Transient

EN61000-4-4, Level 4, Criteria A

Surge Immunity

EN61000-4-5, Level 3, Criteria A

Transportation

ISTA Procedure 1B