Installation and Configuration

14

5.3

Connect the Internal Batteries Using the External Connector

The internal connectors of the internal battery packs will be connected when shipped. However, the

internal batteries will be disconnected from the UPS using a rear panel connector. The connector

attaches to the UPS in both the open and closed position using two screws. The picture on the left

shows the connector in the open position, as shipped.
When the UPS is installed, remove the two screws to release the connector. Plug the connector into

the socket. The internal batteries are now connected to the UPS electronics. Install the two screws to

secure the connector in the closed position.

5.3.1 Storage

If the UPS is to be shipped or stored for an extended time, the connector should be removed and

attached in the open position, as shown above. This will minimize any standby current drain on the

batteries.

5.4

Connect Input/Output Power

The UPS should arrive with the basic hardwire

box attached. If the box needs to be exchanged for

an optional model, remove and install the desired

box using the three captive screws marked in the

illustration at right.
To remove:
Loosen the screws about 20 turns until the box

can be pulled away from the UPS.
To install:
Align the connectors on the box and UPS. Push

the box into place. While holding the box firmly

against the UPS, tighten the three captive screws

until the box is secure. Do not over tighten.

5.4.1 Distribution Box Electrical Connections

Electrical connections are made through a remov-

able power distribution box that attaches to the rear of the UPS.
The installer must provide a 32A branch circuit breaker. The Input circuit breaker on the distribution

box and the Output circuit breaker on the rear fixed-panel of the UPS disconnect all power between

the main cabinet and the distribution box.
Models equipped with a manual bypass switch pass bypass power directly to the bypass switch from

the input terminal block. The input circuit breaker on the distribution box does not disconnect power

from the manual bypass switch.

Remove these screws

to release connector

Unscrew

these

captive

screws