Table 1 electrical specifications, Figure 6, Distribution box electrical connections diagram – Liebert GXT2-6000RT230 User Manual

Page 19: Table 1, Electrical specifications, Output input, 10mm, Use copper wire only

Advertising
background image

Installation and Configuration

15

Figure 6

Distribution box electrical connections diagram

PD-CEHDWR and PD-CEHDWRBYP Terminal Block Connections

Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not

share the same conduit.
Table 1

Electrical specifications

Input

Current

Rating

Recommended

(Maximum) External

Overcurrent Protection

Recommended Wire

(Including ground wire)

(758C copper wire)

Maximum Wire

Accepted by

Terminal Block

Terminal

Tightening

Torque

24A

32A

6-10mm

2

(8-10AWG)

10mm

2

(8AWG)

2.26 Nm (20 in-lb)

NOTE
1. Note1 The installer must provide circuit breaker protection according to local codes. The

mains disconnect should be within sight of the UPS or have appropriate an appropriate

lock-out. Maintain service space around the UPS or use flexible conduit.

2. Note 2 The installer must provide output distribution panels, circuit breaker protection, or

emergency disconnects according to local codes. Output circuits must not share a common

conduit with any other wiring.

Mains

Input

Output

Output

Input

CB

Input

CB

UPS

Output

CB

32A

External

Branch

CB

32A

External

Branch

CB

30

30

30

30

UPS - PFC, Battery, Inverter

UPS - PFC, Battery, Inverter

Byp.

Inv.

PD-CEHDWR

PD-CEHDWRBYP

Mains

UPS

Output

CB

Input

N

N

L

L

N

N

L

L

OUTPUT

INPUT

32Amp Max Branch

Overcurrent Protection

6-10mm

2

- Use Copper Wire Only

OUTPUT TO LOAD

INPUT TO UPS