Configuration Program

17

7.0

C

ONFIGURATION

P

ROGRAM

The final step of installation may require custom configuration of your UPS using the enclosed config-

uration program. Some configuration settings may be changed only while the UPS is off. These should

be set before the UPS is put into full-time service powering the critical load.
For most users operating with 230VAC and with no external batteries, the factory default settings

will be adequate.

7.1

GXT2-6000RT230 and GXT2-4500RT230 Configuration Program Features

• Select one of three L-N output voltages to match local voltages.
• Enable/Disable Auto-Restart.
• Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.
• Set the Low Battery Warning alarm time from 2 to 30 minutes.
• Enable/Disable the Auto-Battery test.
• Set the Auto-Battery test to 7, 14, 21, or 28 days.
• Specify the number of external battery cabinets connected to the UPS to adjust the remaining run

time calculations reported by Liebert software products.

• Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see Table 2).

7.1.1 What You Will Need

In addition to the GXT2 UPS, you will need the configuration program diskette and serial cable (beige

or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. A Win-

dows 95® or later computer, desktop or laptop, is also required to set up and run the configuration

program.