Installation

12

3.8

EPO Switch

The Liebert PSI XR is equipped with an Emergency Power Off (EPO) switch. The user must supply a

means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder breaker to

interrupt all sources of power to the UPS and connected equipment to comply with national and local

wiring codes and regulations.

Figure 13 EPO connection for normally open operation

3.9

External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery

run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked

beneath the UPS. The batteries have a maximum run time of three hours at full load.
1. Install the external battery cabinet in tower- or rack-configuration (see Figure 14 or 3.3 - Rack-

Mount UPS Conversion and Installation).

2. Connect the external battery cabinet cable to the rear of the external battery cabinet, then to the

rear of the UPS (see Figure 15).

Figure 14 Install the external battery cabinet in tower installation

NOTICE

External battery cabinet power connectors are color-coded as noted in Table 1. Do not try to

install external battery cabinets with connectors that are a different color from the battery

connector on the UPS.

Table 1

Battery cabinet connector color key

UPS Model

Nominal System Voltage (connector color)

External Battery Cabine Model

PS1000RT3-120XR

PS1000RT3120XRW

24VDC (Red)

PSRT3-24VBXR

PS1500RT3-120XR

PS1500RT3120XRW

PS2200RT3-120XR

PS2200RT3120XRW

48VDC (Gray)

PSRT3-48VBXR

PS3000RT3-120XR

PS3000RT3120XRW

1

2

1 = EPO+

2 = Ground

Short Pin 1 and Pin 2 to enable the EPO function

Connect the top of the UPS

to the top of the battery cabinet

with the Battery UPS Tab and

hardware

Connect tower stand and set

the UPS and battery cabinet in

them; check to ensure stability

If two or more battery cabinets are

used in a tower setup, the tower stand

must be extended with the spacers

included with each battery cabinet.