Table 8 liebert psi xr battery run times, Table 8, Liebert psi xr battery run times – Liebert UPS Systems PSI XR User Manual

Page 27

Advertising
background image

Specifications

23

Table 8

Liebert PSI XR battery run times

Number of Batteries

Load %

1000VA

1500VA

1920VA

3000VA

Internal Battery

10

82

81

76

75

25

43

32

32

32

50

15

13

14

13

75

9

8

8

8

100

6

5

5

5

Internal Battery

+ 1 External

Battery Cabinets

10

272

222

161

142

25

139

109

80

70

50

73

55

45

31

75

51

31

25

17

100

31

18

15

12

Internal Battery

+ 2 External

Battery Cabinets

10

438

357

241

205

25

231

175

128

106

50

129

95

67

56

75

84

61

47

31

100

65

46

29

18

Internal Battery

+ 3 External

Battery Cabinets

10

614

492

322

267

25

324

241

170

139

50

181

131

95

73

75

126

84

62

50

100

96

64

48

31

Internal Battery

+ 4 External

Battery

Cabinets

10

789

627

483

329

25

385

308

255

171

50

233

167

143

95

75

162

114

100

62

100

124

82

72

47

Internal Battery

+ 5 External

Battery Cabinets

10

964

762

564

392

25

509

374

298

204

50

285

203

167

113

75

197

139

116

74

100

151

106

84

56

Internal Battery

+ 6 External

Battery Cabinets

10

1140

897

644

454

25

601

440

341

236

50

336

239

191

131

75

233

163

133

85

100

179

124

102

65

Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.