0 battery maintenance, 1 battery charging, storage, 2 internal battery replacement procedure – Liebert UPS Systems PSI XR User Manual

Page 24: Figure 18 battery replacement, Attery, Aintenance, Battery charging, storage, Internal battery replacement procedure, Notice

Advertising
background image

Battery Maintenance

20

7.0

B

ATTERY

M

AINTENANCE

7.1

Battery Charging, Storage

The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their

design life. The Liebert PSI XR continuously charges the batteries when connected to the utility sup-

ply, even while the UPS is switched Off.
If the Liebert PSI XR will be stored for an extended period, Liebert recommends connecting the UPS

to input power for at least 8 hours every four to six months to keep the batteries charged.

7.2

Internal Battery Replacement Procedure

NOTICE

This UPS is equipped with internal batteries that the user can replace without shutting down

the UPS or connected loads (hot swappable). Caution must be exercised when replacing the

batteries because the load is unprotected from power fluctuations and power failures.

To replace the batteries:
1. Remove the two screws on the left side of the front bezel.
2. Pull the front bezel off the UPS.
3. Remove the screw on the battery connectors holder.
4. Remove the two screws on the battery bracket.
5. Disconnect the two slotted, red/gray and black battery connectors.
6. Grasp the battery pack assembly by the handle and pull it out of the front of the UPS.
7. Unpack the new battery assembly, taking care not to destroy the packing.
8. Compare the new and old battery assemblies to make sure they are the same. If so, proceed with

replacement. If they are different, STOP and contact your local dealer, Emerson representative or

Liebert Applications.

9. Slide the new battery pack into the UPS.
10. Reattach the battery bracket with the two screws.
11. Reconnect the slotted, red/gray and black battery connectors.
12. Reinsert the screw on the battery connectors holder.
13. Reattach the front bezel.

Figure 18 Battery replacement

Load Level

Battery Level

Load L

evel

Batter

y Leve

l

Load Level

Battery Level

Load Level

Battery Level

Step 1

Step 2

Step 3

Step 4

Advertising