Liebert UPStation GXT User Manual
Page 11
Advertising
7
Connecting Maintenance Bypass to UPStation GXT6000T - 208
1
2
3
4
MAINTENANCE BYPASS
GND1
208
VAC
GND3
GND2
Utility
TB1
UPS output
TB3
UPS input
TB2
2
1
3
2
1
3
2
1
3
4
L1
L2
L1
L2
+
-
Input
Output
Ext. battery
Utility
input
L1
L2
NOTE
GMB12 models are supplied
with an attached input power
cord complete with L14-30
plug.
GXT6000T - 208
Output
TB4
NOTE
When using the Maintenance
Bypass with an UPStation
GXT6000T-208, a jumper
(included with the accessory
kit) must be connected to the
TB3 (UPS output) terminal
block on the Maintenance
Bypass between TB3-1 and
TB3-2, as shown.
Advertising