Hardwire output option, Accessing terminal block, Ardwire – Liebert UPStation GXT User Manual

Page 15: Utput, Ption

Advertising
background image

11

HARDWIRE OUTPUT OPTION

This product is intended to be installed by a
qualified electrician only.
1. COMPLETELY REMOVE ALL POWER FROM

THE FRAME. If the Maintenance Bypass is
connected to the UPS, disconnect external
battery supply.

2. Remove the end cover plate to access the

terminal block (see Accessing terminal
block
below).

3. Without disconnecting from the terminal block,

unscrew and pull out the hardwire plate(s).

4. Route all wires from the hardwire plate(s) to

the terminal block.

5. Connect the GROUND wire to the grounding

bar strip (GND1).

6. Connect the remaining wires in accordance

with the wiring diagram (located inside the
base enclosure).

7. Replace the receptacle plates and the end

cover plate, using care to not damage the
wires.

Accessing terminal block

NOTE
When wiring 120 V loads, LINE must be

alternated between TB4-1 and TB4-3 to

balance the 120V load. Connect all

neutral wires to TB4-4.