PERATION

Figure 4

Operation controls and indicators

Status LED Indicators—Green and red LEDs for each protected phase provide a visual status

summary of all surge modules within device.
Full Protection LEDs—Green LEDs are illuminated only when all surge components are at

100% percent efficiency.
Reduced Protection—Red LED illuminated only when protection has been reduced by off-line

surge components such as open fuse links.
Built-In Component Integrity Test (BICIT)—While the monitoring circuitry provides visual

status during operation, the built-in test circuitry will verify that every fuse link and associated

MOV is operational. The built-in-test may be operated easily by simply pressing one push button

during normal operation. The BICIT cycles through each phase bank including neutral-ground

sending out a test request signal to all modules. If all fuse links are in intact the red reduced-pro-

tection LED for the particular bank in test will illuminate for a two to four seconds. Should this

light stay lit for more than 5 seconds, one module in that bank has at least one open fuse link.
While testing, the Test LED will illuminate. Also, during the built-in test sequence, the alarm

should sound for each bank. Pressing the alarm disable switch before or during the test will

silence the alarm.
Sonic Alarm—If one or more of the surge modules require replacement, an audible alarm is acti-

vated to draw attention to the fact that repair service is required to restore the system to normal

operation. An audible alarm disable button is provided to silence the alarm. The system will auto-

matically reset itself after repair.

Table 4

Monitoring features

Monitoring Features

“S” Package

“C” Package

“D” Package

LED Status Indicators

Built-In Component Integrity Test

(BICIT)

Sonic Alarm

Form C Dry Contacts

Surge Counter

Swell Counter

Remote Monitor Panel

Optional

Optional

Optional